Airflow measurement – change of coefficient K
8.14
For each of the operation modes (CAV, VAV, COP), an airflow measurement is possible. To do this, the
selection of the fans was configured in the factory in the programmable logic controller. Each unit is thus
defined by its coefficient k defined by its fans.
Coefficient K values
RHE 1300: K=65
RHE 1900: K=93
RHE 2500: K=116
RHE 3500: K=148
Centralized Technical Control (GTC) connection
8.15
The controller in its standard version has an integrated RS485
communication port (to be used with an STP cable).
The standard CORRIGO controller can communicate in Modbus via its
RS485 port by simply activating an internal parameter.
Modbus exchange table
Consult our site