ENGLISH
34
NT_51897201_RHE-AN_130516.docx
Parameter
Heating mode
constant
supply air T°C
Parameter
Heating mode
Room T°C control
Parameter
Heating mode
Constant Supply air T°C with
outdoor T°C compensation
-30
-20
14
-10
0
10
20
18
22
26
Constant supply air temperature maintenance
8.5
The temperature control is driven from the comparison between the supply
air temperature and the set point value parameterized via the console.
Constant ambient temperature maintenance
8.6
The supply is controlled in cascade with the ambient temperature.
The difference between the ambient temperature and the set point
determines the supply temperature.
Therefore, the controller tries to respond to a request to hold the
temperature in an ambiance while limiting the in-duct temperature, which
remains in an allowable range (12-30C°).
Temperature set point adaptation vs. outdoor temperature
8.7
The controller’s operation is similar to the 1st case.
The difference consists of not defining only one temperature set point, but
a compensation curve itself defined in the factory with 8 set points.
The supply set point is then adapted with respect to this curve,
but the override of plus or minus 3°C possible from the main
screen still remains effective.
Initial temperature setpoint
8.8
An initial set point value can be defined from the ‘’Temperature’’ screen in the menus
From the main screen the user can override by +/- 3°C this initial set point
Outdoor air temperature
Compensation curve
Su
ppl
y
21.4°C
2012-06-26 14:02
2500 m3/h
2500 m3/h
Run mode : On
Main screen :
Menu
21.4°C
2012-06-26 14:02
2500 m3/h
2500 m3/h
Run mode : On
Select
''Température" menu
Select the text to modify
the temperature setpoint
OK
.
0
8
7
9
4
5
6
3
2
1
Enter PIN code:
Cancel
1111
OK
.
0
8
7
9
4
5
6
3
2
1
temperature setpoint
Cancel
°C
Set Temperature
value
and select OK
insert Temperature setpoint :
Main screen :
Acces to
adjustment menu
Menu screen :
Enter PIN code: 1111
and select : OK
pass word :
+19.4°C
+21.9°C
+19.8°C
Temperature
Ventilation control
Desired (SetP.)
Room
Outdoor
Constant supply air