8.2. MODBUS MEMORY MAP
Holding registers
N°REG.
Register
Min. Max.
Description
Default
Comments
0
TipoMotor
0
1
0=AC
1=DC
1
Motor type
1
ModoFun
0
7
0=PI_Presión
1=PI_Caudal
2=Proporcional
3=Max-Min
4=PI_Presión+RTC
5=PIRTC
6=PropoRTC
7=Max-Min+RTC
0
Operation mode
2
SensorPI
0
4
0=Interno
1=IN1 0-10V
2=IN1 4-20mA
3=IN2 0-10V
4=IN2 4-20mA
0
Sensor type in PI
PRESSURE or PI VOLUME
mode
3
Sensor1
0
7
0=NO
1=0-10V %HR
2=4-20mA %HR
3=0-10V °C
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
7=NTC 100K
0
Sensor type in
PROPORTIONAL mode
and analog input signal 1
4
Sensor2
0
6
0=NO
1=0-10V %HR
2=4-20mA %HR
3=0-10V °C
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
0
Sensor type in
PROPORTIONAL mode
and analog input signal 2
5
PIRange
50
50
100
1250
2500
9900
SensorPI=0
SensorPI<>0
Sensor<>0
400
(CAB-125/150/160 ECOWATT)
500
(CAB-200/315 ECOWATT)
650
(CAB-250 ECOWATT)
550
(CAB-355/400 ECOWATT)
Range sensor in PI
PRESSURE mode
6
SetPoint
0
5
0=Interno
1=IN1 0-10V
2=IN1 4-20mA
3=IN2 0-10V
4=IN2 4-20mA
5=ConsolaMODBUS
(PROSYS ECOWATT)
5
Set point in PI PRESSURE
mode
7
Kp
1
250
Increases 1
20
Proportional constant in PI
PRESSURE mode
8
Ki
1
250
Increases 1
20
Integral constant in PI
PRESSURE mode
9
Kq
50
300
Increases 1
50
(CAB-125 ECOWATT)
56
(CAB-150/160 ECOWATT)
81
(CAB-200 ECOWATT)
88
(CAB-250 ECOWATT)
108
(CAB-315 ECOWATT)
136
(CAB-355 ECOWATT)
81
(CAB-400 ECOWATT)
Airflow constant with
pressure sensor
10
PulsosEncoder
0
16
Increases 1
2
5
1
Number of pulses for
encoder lap
11
MinOut
0
50
Increases 5%
25
Minimum output value
12
MaxOut
50
100
Increases 5%
100
Maximum output value
13
S1Alarm
0
100
Increases 5%
90
Analog input 1 alarm
14
S2Alarm
0
100
Increases 5%
90
Analog input 2 alarm