SENSOR
< INTERNAL OK
SENSOR
<IN1 0-10V OK
SENSOR
<IN1 4-20mA OK
SENSOR
<IN2 0-10V OK
SENSOR
<IN2 4-20mA OK
OK
OK
Sensor: Sensor type
-
INTERNAL:
Pressure differential internal sensor
- IN1 0-10V:
External sensor with analog signal 0-10V (J5 terminal)
- IN1 4-20mA:
External sensor with analog signal 4-20mA (J5 terminal)
- IN2 0-10V:
External sensor with analog signal 0-10V (J6 terminal)
- IN2 4-20mA:
External sensor with analog signal 4-20mA (J6 terminal)
RANGE
< 400Pa
OK
Press
or
to manually modify the parameter.
The value displayed corresponds to the scale of the
internal sensor factory pre-set. In an external sensor is
installed, introduce the corresponding range.
OK
OK
SET POINT
< INTERNAL OK
SET POINT
<CONSOLE OK
SET POINT
<IN1 0-10V OK
SET POINT
<IN1 4-20mA OK
SET POINT
<IN2 0-10V OK
OK
OK
SET POINT
<IN2 4-20mA OK
Set Point:
-
INTERNAL
-
CONSOLE:
Value set by PROSYS ECOWATT console. Factory set value
- IN1/IN2 0-10V:
Value set by external potentiometer (0-10V)
- IN1/IN2 4-20mA:
Value set by external potentiometer (4-20mA)
PARAMETERS
< Kq=133
OK
Press
or
to manually modify this parameter.
It is advised not to modify.
OK
OK
<INTERNAL
CONSOLE