![S&P CAB ECOWATT PLUS Скачать руководство пользователя страница 127](http://html1.mh-extra.com/html/sandp/cab-ecowatt-plus/cab-ecowatt-plus_manual_3102488127.webp)
NL
127
8.2. GEHEUGENKAART MODBUS
Holding registers
Reg.nr.
Register
Min. Max.
Beschrijving
Standaardinstelling
Opmerkingen
0
TipoMotor
0
1
0=AC (wisselstroom)
1=DC (gelijkstroom)
1
Motortype
1
ModoFun
0
7
0=PI_Druk
1=PI_Volume
2=Proportioneel
3=Max-Min
4=RTC
5=PIRTC
6=ProporRTC
7=Max-Min+RTC
0
Bedrijfsmodus
2
SensorPI
0
4
0=Intern
1=IN1 0-10V
2=IN1 4-20mA
3=IN2 0-10V
4=IN2 4-20mA
0
Sensortype in PI_DRUK of
PI_VOLUME-modus
3
Sensor1
0
7
0=GEEN
1=0-10V %HR
2=4-20mA %HR
3=0-10V °C
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
7=NTC 100K
0
Sensortype in
PROPORTIONELE modus
en analoog ingangssig-
naal 1
4
Sensor2
0
6
0=GEEN
1=0-10V %HR
2=4-20mA %HR
3=0-10V °C
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
0
Sensortype in
PROPORTIONELE modus
en analoog ingangssig-
naal 2
5
PIRange
50
50
100
1250
2500
9900
SensorPI=0
SensorPI<>0
Sensor<>0
400
(CAB-125/150/160 ECOWATT)
500
(CAB-200/315 ECOWATT)
650
(CAB-250 ECOWATT)
550
(CAB-355/400 ECOWATT)
Rangesensor in PI DRUK-
modus
6
SetPoint
0
5
0=Intern
1=IN1 0-10V
2=IN1 4-20mA
3=IN2 0-10V
4=IN2 4-20mA
5=ConsolaMODBUS
(PROSYS ECOWATT)
5
Geprogrammeerd instel-
punt in PI DRUK-modus
7
Kp
1
250
Stappen van 1
20
Proportioneel constant in
PI DRUK-modus
8
Ki
1
250
Stappen van 1
20
Integraal constant in PI
DRUK-modus
9
Kq
50
300
Stappen van 1
50
(CAB-125 ECOWATT)
56
(CAB-150/160 ECOWATT)
81
(CAB-200 ECOWATT)
88
(CAB-250 ECOWATT)
108
(CAB-315 ECOWATT)
136
(CAB-355 ECOWATT)
81
(CAB-400 ECOWATT)
Luchtdebiet constant met
druksensor
10
PulsosEncoder
0
16
Stappen van 1
2
5
1
Aantal pulsen per omwen-
teling encoder
11
MinOut
0
50
Stappen van 5%
25
Minimale uitgangswaarde
12
MaxOut
50
100
Stappen van 5%
100
Maximale uitgangswaarde
13
S1Alarm
0
100
Stappen van 5%
90
Alarm analoge ingang 1