S&C Instruction Sheet 461-521    7

Quick Pairing Guide 

 The TripSaver II Cutout-Mounted Recloser provides superior protection for overhead 
lateral circuit protection. Pairing a TripSaver II recloser with the TripSaver II® 
Communications Gateway allows remote access to that recloser via DNP3 protocol 
messaging delivered by the customer’s communications network. The data provided 
by the communications gateway enables faster and more efficient responses to power 
system outages and can help optimize maintenance scheduling and momentary outage 
and permanent outage management.

One communications gateway can be paired with up to four TripSaver II reclosers 

using encrypted IEEE 802.15.4 wireless communications. To pair with the communica-
tions gateway, these reclosers must be installed maximum distance of 100 feet (30.5 
meters) from the communications gateway. (A 25 to 30 foot (7.6 to 9.1 meter) distance is 
more common depending on pole height and local construction practices.) The reclosers 
must also be furnished with the 

Extended Open Interval 

option, which allows up to a 

30-second open interval between 

Reclose

 operations and have 

Gateway

 mode enabled 

using the service center configuration software.

Overview

 Before pairing a TripSaver II Cutout-Mounted Recloser with a TripSaver II Communications 
Gateway, it must be placed in 

Gateway

 mode at the service center. To enable 

Gateway

 

mode:

STEP  1.  

Connect to the TripSaver II recloser using the service center configuration 
software and the service center configuration kit. (USB transceiver, corded 
power module, and ac adapter.) Detailed instructions for connecting a TripSaver 
II recloser using the service center configuration software can be found in S&C 
Instruction Sheet 461-504.

STEP  2.  

Navigate to the  

Communication Settings

 menu and click on the 

Communication Mode dropdown box. Change the 

Communication

 mode to 

“Gateway Mode.”

STEP  3.  

Click on the 

Apply Communication Mode

 button. 

Note:

 The A

pply 

Communication Mode

 button will not apply any changes made on any other 

menu screens. If changes have been made to another menu screen, such as the 

TCC Curve Settings

 screen, click on the 

Apply

 button, see Figure 1.

STEP  4.  

The TripSaver II recloser is now in 

Gateway

 mode and can be paired with a 

TripSaver II Communications Gateway. Disconnect the TripSaver II recloser 
from the TripSaver II Service Center Configuration Software by clicking on the 

Disconnec

t button and unplugging the USB transceiver.

Placing a TripSaver II 

Recloser in Gateway 

Mode

Figure 1. Enabling Gateway Mode in the TripSaver II recloser.

Содержание TripSaver II

Страница 1: ...rstanding Safety Alert Messages 3 Following Safety Instructions 3 Replacement Instructions and Labels 3 Location of Safety Labels 4 Safety Precautions 5 Shipping and Handling Packing 6 Inspection 6 Ha...

Страница 2: ...ns Gateway Designate a location where you can easily retrieve and refer to this publication Proper Application WARNING The equipment in this publication is only intended for a specific application The...

Страница 3: ...recautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions I...

Страница 4: ...for Safety Labels Location Safety Alert Message Description Part Number A DANGER TripSaver II may be energized from either side and in any position G 9473 E B CAUTION This control is connected to ele...

Страница 5: ...ctric shock and death DANGER The TripSaver II Cutout Mounted Recloser operates at high voltage Failure to observe these precautions will result in serious personal injury or death Some of these precau...

Страница 6: ...TICE DO NOT drop a TripSaver II recloser or subject any of its parts to undue stress during installation Only remove a TripSaver II recloser from the carton when you are ready for installation Storage...

Страница 7: ...rvice center configuration software Overview BeforepairingaTripSaverIICutout MountedRecloserwithaTripSaverIICommunications Gateway it must be placed in Gateway mode at the service center To enable Gat...

Страница 8: ...s Gateway with a PC Ethernet cable Figure 2 Connect an Ethernet cable to the gateway controller module STEP 2 The communications gateway is accessed using a web browser interface The defaultconfigurat...

Страница 9: ...from the command prompt With the CAT5 cable attached to communications gateway Ethernet Port 1 launch a Web browser on the PC Within the URL address line type in the communications gateway default IP...

Страница 10: ...h firmware version 1 6 or 1 7 pairing can only be performed with the TripSaver II recloser powered by line current or an external power source not supplied by S C For details on the specifications for...

Страница 11: ...asily paired in the service center without the requirement of line current or an external power source using the corded power module and ac adapter from the service center configuration kit STEP 1 Pla...

Страница 12: ...e 9 This will turn on communications inside the TripSaver II recloser allowing it to be paired with the communications gateway Figure 9 Attach the magnet tool to the green logo STEP 4 Navigate to the...

Страница 13: ...n be used at the installation site on TripSaver II reclosers furnished with firmware version 1 8 installed on the utility pole and NOT powered by line current by using the cordless power module to sup...

Страница 14: ...on the Device Management screen STEP 2 With the recloser removed from the utility pole connect to the TripSaver II recloser using the service center configuration software and the service center confi...

Страница 15: ...rvice center configuration software can be found in S C Instruction Sheet 461 504 STEP 4 Navigate to the Communication Settings menu and click on the Communication Mode dropdown box Change the Communi...

Отзывы: