S&C TripSaver II Скачать руководство пользователя страница 11

S&C Instruction Sheet 461-521    11

Quick Pairing Guide

Figure 7. The Device Management screen.

STEP  4.  

Click on the 

Add TripSaver II Cutout-Mounted Recloser

 button. A pop-up 

menu will appear.

STEP  5.  

Enter the TripSaver II recloser’s transceiver ID and device name.

Note:

 The device name can be anything but is usually a description of where 

the TripSaver II recloser is installed.

STEP  6.  

Click on the 

OK

 button. The communications gateway will connect to the 

TripSaver II recloser and it will appear as “connected” in the 

Device 

Management 

screen. See Figure 8.

Figure 8. The Device Management screen after pairing a TripSaver II recloser.

Service Center Pairing of the TripSaver II Recloser Furnished with 

Firmware Version 1.8

With the introduction of TripSaver II recloser firmware version 1.8, the recloser and 
communications gateway can now be easily paired in the service center without the 
requirement of line current or an external power source using the corded power module 
and ac adapter from the service center configuration kit:

STEP  1.  

Place the TripSaver II recloser in 

Gateway

 mode, as described on page 7. Power 

the communications gateway by connecting it to an ac power source. Connect 
to the communications gateway with a PC, as described on page 8. Make sure 
any nearby USB transceiver is unplugged.

STEP  2.  

Power the TripSaver II recloser to be paired with the corded power module. 
Instructions for using the power module can be found in S&C Instruction Sheet 
461-504.

Note: 

The pairing process should take approximately 5 minutes. It could take up to   

15 minutes. Refresh the browser after 5 minutes to make the paired TripSaver 
II recloser in the 

Device Management 

screen show its “connected” status. If the  

TripSaver II recloser does not show “connected” after waiting 15 minutes, follow the 
“Pairing Process Takes Longer Than Expected” instructions in the Troubleshooting 
section on page 15.

Содержание TripSaver II

Страница 1: ...rstanding Safety Alert Messages 3 Following Safety Instructions 3 Replacement Instructions and Labels 3 Location of Safety Labels 4 Safety Precautions 5 Shipping and Handling Packing 6 Inspection 6 Ha...

Страница 2: ...ns Gateway Designate a location where you can easily retrieve and refer to this publication Proper Application WARNING The equipment in this publication is only intended for a specific application The...

Страница 3: ...recautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions I...

Страница 4: ...for Safety Labels Location Safety Alert Message Description Part Number A DANGER TripSaver II may be energized from either side and in any position G 9473 E B CAUTION This control is connected to ele...

Страница 5: ...ctric shock and death DANGER The TripSaver II Cutout Mounted Recloser operates at high voltage Failure to observe these precautions will result in serious personal injury or death Some of these precau...

Страница 6: ...TICE DO NOT drop a TripSaver II recloser or subject any of its parts to undue stress during installation Only remove a TripSaver II recloser from the carton when you are ready for installation Storage...

Страница 7: ...rvice center configuration software Overview BeforepairingaTripSaverIICutout MountedRecloserwithaTripSaverIICommunications Gateway it must be placed in Gateway mode at the service center To enable Gat...

Страница 8: ...s Gateway with a PC Ethernet cable Figure 2 Connect an Ethernet cable to the gateway controller module STEP 2 The communications gateway is accessed using a web browser interface The defaultconfigurat...

Страница 9: ...from the command prompt With the CAT5 cable attached to communications gateway Ethernet Port 1 launch a Web browser on the PC Within the URL address line type in the communications gateway default IP...

Страница 10: ...h firmware version 1 6 or 1 7 pairing can only be performed with the TripSaver II recloser powered by line current or an external power source not supplied by S C For details on the specifications for...

Страница 11: ...asily paired in the service center without the requirement of line current or an external power source using the corded power module and ac adapter from the service center configuration kit STEP 1 Pla...

Страница 12: ...e 9 This will turn on communications inside the TripSaver II recloser allowing it to be paired with the communications gateway Figure 9 Attach the magnet tool to the green logo STEP 4 Navigate to the...

Страница 13: ...n be used at the installation site on TripSaver II reclosers furnished with firmware version 1 8 installed on the utility pole and NOT powered by line current by using the cordless power module to sup...

Страница 14: ...on the Device Management screen STEP 2 With the recloser removed from the utility pole connect to the TripSaver II recloser using the service center configuration software and the service center confi...

Страница 15: ...rvice center configuration software can be found in S C Instruction Sheet 461 504 STEP 4 Navigate to the Communication Settings menu and click on the Communication Mode dropdown box Change the Communi...

Отзывы: