S&C Instruction Sheet 461-521 13
Quick Pairing Guide
STEP 6.
Enter the TripSaver II recloser’s transceiver ID and device name.
Note:
The device name can be anything but is usually a description of where
the TripSaver II recloser is installed.
STEP 7.
Click on the
OK
button. It will take between one and 5 minutes for the
communications gateway to connect to the TripSaver II recloser. The recloser
will appear in the
Device Management
screen after the screen is refreshed
using the browser’s
Refresh
button. See Figure 11.
Figure 11. The Device Management screen after pairing TripSaver II recloser.
Note:
This method can be used at the installation site on TripSaver II
reclosers furnished with firmware version 1.8 installed on the utility pole
and NOT powered by line current by using the cordless power module to
supply power to the recloser and then applying the magnet tool. In no case
should the corded power module be used at the installation site with the
TripSaver II recloser installed on the utility pole.
Note:
The pairing process should take approximately 5 minutes. It
could take up to 15 minutes. Refresh the browser after 5 minutes to make
the paired TripSaver II recloser in the
Device Management
screen show its
“connected” status. If the TripSaver II recloser does not show “connected”
after waiting 15 minutes, follow the “Pairing Process Takes Longer Than
Expected” instructions in the Troubleshooting section on page 15.