Pushbutton Operation

Use the following procedure to operate the various Scada-
Mate SD switch pushbuttons:

STEP  21.  

All S&C control units and most control units of 

other manufacture have a 

Local/Remote

feature. To operate, place the LOCAL/REMOTE 
switch inside the control unit to the 

Local 

position. Refer to the instruction sheet furnished 
with the control unit. The switch can now only be 
operated locally. 

Then, press the OPEN or CLOSE pushbut-

ton as appropriate. See Figure  15. The inter-
rupter OPEN/CLOSED indicator on the end 
of the Scada-Mate SD switch base indicates 
interrupter contact position: the target with 
an “O” indicates the interrupters are in the 

Open 

position; the target with a “C” indicates 

the interrupters are in the 

Closed

 position. 

The indicator does not show status of the 
disconnects.

Remote Operation

Use the following procedure to set up the Scada-Mate SD 
switch for remote operation:

STEP  22.  

Place the LOCAL/REMOTE switch inside the 

control unit in the 

Remote

 position. Refer to the 

instruction sheet furnished with the control unit. 

The Scada-Mate SD switch can now only be 

operated by remote supervisory control. By using 
the SCADA system, the dispatcher can test the 
electrical operation of the switch and the entire 
SCADA control path, including communications. 
See Figure 15. The interrupter OPEN/CLOSED 
indicator on the end of the Scada-Mate SD switch 
base indicates interrupter contact position: the 
target with an “O” indicates the interrupters are 
in the 

Open 

position; the target with a “C” indi-

cates the interrupters are in the 

Closed

 position. 

The indicator does not show the status of the 
disconnects. See Figure 16.

Figure 16. The optional disconnect.

Figure 15. Operating the switch using the LOCAL/REMOTE switch
inside the CCU.

The switch control includes OPEN/CLOSE 

pushbuttons, switch-position indicating 

lamps, disconnect closed and latched 

indicating lamps, a LOCAL/REMOTE 

switch, and an operation counter

Operation—For Switches with Power Operator

Disconnect

Pole-unit

OPEN/

CLOSED

indicator

Содержание Scada-Mate SD

Страница 1: ...eplacement Instructions and Labels 3 Location of Safety Labels and Tags 4 Safety Precautions 5 Shipping and Handling Packing 6 Inspection 6 Handling 7 Installation Inserting Pole Mounting Hardware 8 S...

Страница 2: ...retrieve and refer to this publication Proper Application WARNING The equipment in this publication is only intended for a specific application The application must be within the ratings furnished for...

Страница 3: ...cautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If...

Страница 4: ...ads may be energized from either side and in any position G 6812 D WARNING Electrocution Hazard Switch and control unit enclosure must be installed and grounded ONLY by qualified personnel G 6815 E WA...

Страница 5: ...Switching Systems contain fast moving parts that can severely injure fingers Do not remove or disassemble operating mechanisms or remove access panels on the Scada Mate SD switch base unless directed...

Страница 6: ...ese values must be programmed into the remote terminal unit RTU installed with the switch if applicable to apply correction for the unit to unit variations in the sensors The S C Sensor information is...

Страница 7: ...EP 2 Secure the lifting slings to the switch before unbolting the switch from the crate Remove all packing materials before lifting the switch Shipping and Handling Lifting bracket extended NOTICE Do...

Страница 8: ...erline distance of the holes must be 14 inches 356 mm STEP 4 Insert two inch diameter through bolts not furnished in the holes drilled in Step 3 Secure these bolts loosely with necessary washers and n...

Страница 9: ...to uncrate the switch before lifting may cause damage to the switch or personal injury Installing the Optional Pole Band and J Bolts Conduct the following steps to install the optional pole band and...

Страница 10: ...ting the end of a number 2 AWG wire or two number 6 AWG wires or wires having an equivalent cross sectional area to the grounding lug on the pole saddle See Figure 6 Insert the ground wire into the gr...

Страница 11: ...ors on the terminal pads use the following procedure to prepare their surfaces STEP 10 Do not wire brush Scada Mate SD switch terminal pads They are plated and wire brushing will scratch the protectiv...

Страница 12: ...to the terminal pads For installation instructions refer to S C Drawing RD 6794 STEP 13 To install the optional wildlife protection components first prepare the surfaces of the terminal pads and conn...

Страница 13: ...Mate SD switches STEP 15 Ground the enclosure by solidly connecting one number 6 AWG wire or wires of equivalent cross sectional area to the ground lug on the back of the enclosure Solidly connect th...

Страница 14: ...ol unit Locate the connector receptacle on the front of the switch base and remove the dust cover c Remove the sensor shorting blocks from the receptacle and attach the control cable plug d Secure the...

Страница 15: ...rol cable at the drip loop and at the switch connection b Attach the control cable along the length of the utility pole and secure the control cable to the utility pole using suitable guards or clamps...

Страница 16: ...Electric Company Use the following procedure to energize the power operated switch STEP 20 After making all user connections to the control unit if applicable in accordance with the S C instruction sh...

Страница 17: ...remote operation STEP 22 Place the LOCAL REMOTE switch inside the control unit in the Remote position Refer to the instructionsheetfurnishedwiththecontrolunit The Scada Mate SD switch can now only be...

Страница 18: ...ow the procedure below using a conventional insulated hookstick or S C Universal Pole and Pole Extension if required fit ted with a heavy duty hook tool such as the S C Substation Prong or equivalent...

Страница 19: ...gency Manual Operation STEP 26 Scada Mate SD Switches are capable of manual interrupter operation In the event of electrical power loss a standard or extendible hookstick is used to open and close the...

Страница 20: ...uffix W slide the tap cover backfarenoughtogainaccesstotheterminalpads Then remove the upper and lower terminal pad covers to permit the removal of the phase conductors Retain the covers for reinstall...

Отзывы: