S&C Instruction Sheet 775-510
15
Security belt
Padlock (provided
by others)
Drip loop
(maintain a 9-inch
(229-mm) minimum
radius when bending
the control cable)
Figure 13. Connecting the control cable to the control unit
enclo sure.
STEP 18.
Form a drip loop with the control cable where it
attaches to the control unit.
(a) Maintain a 9-inch (229-mm) minimum radius
when bending the control cable at the drip loop
and at the switch connection.
(b) Attach the control cable along the length of the
utility pole and secure the control cable to the
utility pole using suitable guards or clamps.
(c) Form a coil with any excess control cable,
maintaining a 9-inch (229 mm) minimum radius,
and secure it to the utility pole. See Figure 13.
STEP 19.
A stainless steel security belt is included with
the control unit for padlocking the multi-pin
connector to the control unit. See Figure 12 on
page 14. Place the security belt around the
connector between the connector clips and the
enclosure, and insert a padlock (not furnished)
through the holes provided. See Figure 13.
Installation