Using the Communications Card
The actual left-source and right-source phase voltages, zero-sequence voltages,
positive-sequence voltages, and negative-sequence voltages after normalizing are
displayed.
The field adjustable items in the
Voltage
data window which can be changed using
Matlink include
Loss of Source Level, Return of Source Level, Unbalance Level,
and Overvoltage Level
.
Step 9
If
Lockout Option
has been factory-set for “Internal,” click on the
Current
button bar.
The
Current
data window will appear, similar to that shown below.
The
Lockout Level
is field adjustable using Matlink.
Step 10
Click on the
Time
button bar. The
Time
data window will appear, similar to that shown
below.
12
S&C Instruction Sheet 515-506