S&C IntelliCap Скачать руководство пользователя страница 6

6

    S&C Instruction Sheet 1022-510 

Applicable Software

This instruction sheet was prepared for use with IntelliCap 
software:

 ICAP109S

 and 

IVAR109S

.

Software identification is shown on the IntelliLink

®

 Setup 

Software 

Troubleshooting>Control & Switch Information

 

screen. For questions regarding the applicability of informa-
tion in this instruction sheet to future product releases, please 
contact S&C Electric Company.

Pre-Installation Checklist

Before installing the IntelliCap control, carry out the following 
steps in the shop:

STEP 1. 

Inspect the control for visible damage.
Make sure there is no obvious damage to the  
control enclosure or any internal components.

STEP 2. 

Check whether a sensor cable may be needed.
With var sensing, the control may require a 
connection cable for the sensors.

STEP 3. 

Use the required setup software and equipment.

It is possible to use the faceplate switches 

and LCD screen for initial setup of an IntelliCap 
control, but using IntelliLink software is easier 
and faster. The faceplate switches can be used for 
later adjustments in the field. Equipment needed 
includes:

•  A personal computer

 The computer should 

have a Microsoft Windows

®

 7 or 10 operating 

system, Internet Explorer 5.0 or higher, 32 MB of 
RAM, a USB or serial port, and Internet access to 
the S&C Automation Customer Support Portal.

•  A serial communication cable

 This cable 

connects the computer to the LOCAL COMM 
PORT on the control. Use a straight-through 
cable, not a null-modem cable. The  cable must 
be long enough to connect to an installed  
IntelliCap control.

The serial connection is RS232 with a  

DB9-pin connector.

If the computer only has USB ports, use a 

serial-to-USB cable adapter.

STEP 4. 

Do one of the following:
•  Go to the installation site and install the  

IntelliCap control. Then  configure the control 
as described in Instruction Sheet 1022-530, ”S&C  
IntelliCap

®

 Automatic Capacitor Control: 

Setup

.”

•  Complete the configuration steps summarized 

in the “Optional In-Shop Setup” section while 
you are in the shop. Then install the control at 
the site.

Optional In-Shop Setup

The following steps can be completed while you are still in 
the shop or later at the installation site:

STEP 1. 

Install the IntelliLink software on your computer.

For details, see the “Install the IntelliLink 

Software” section in Instruction Sheet 1022-530, 
“S&C IntelliCap

®

 Automatic Capacitor Control: 

Setup

.”

STEP 2. 

Configure the control software.

Most of the software setup can be done in the 

shop. For an explanation of how to configure 
the software, see the “Setting Up the Capacitor 
Control”

 

section in Instruction Sheet 1022-530, S&C 

IntelliCap

®

 Automatic Capacitor Control: 

Setup

.”

Installation

Содержание IntelliCap

Страница 1: ...uctions 4 Replacement Instructions and Labels 4 Safety Precautions 5 Installation Applicable Software 6 Pre Installation Checklist 6 Optional In Shop Setup 6 Installing the Current Sensor var only 7 Onsite Installation 9 Meter Base Mounting 10 Bracket Mounting 14 Testing Capacitor Bank Operation 17 Setting the Control for Manual Operation 17 Wiring Diagrams 18 NOTICE The latest instruction sheets ...

Страница 2: ... standard conditions of sale as set forth in Price Sheets 150 and 181 applies to the S C IntelliCap Automatic Capacitor Control except that the first paragraph of the said warranty is replaced by the following 1 General The seller warrants to the immediate purchaser or end user for a period of 10 years from the date of shipment that the equipment delivered will be of the kind and quality specified...

Страница 3: ...user all manufacturer s warranties that apply to such major components Warranty of equipment services packages is contingent upon receipt of adequate informa tion on the user s distribution system sufficiently detailed to prepare a technical analysis The seller is not liable if an act of nature or parties beyond S C s control negatively impact performance of equipment services packages for example...

Страница 4: ...ry if instructions including recommended precautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed If you do not understand any portion of this instruction sheet and need assistance contact your nearest S C Sales Office or S C Authorized Distributor Their tele phone numbers are listed on...

Страница 5: ...omatic Capacitor Control must be restricted only to Qualified Persons 2 SAFETY PROCEDURES Always follow safe operating proceduresandrules Alwaysmaintainproperclearance from energized components 3 PERSONAL PROTECTIVE EQUIPMENT Always use suitable protective equipment such as rubber gloves rubber mats hard hats safety glasses arc flash clothing and fall protection in accordance with safe operating p...

Страница 6: ...B of RAM a USB or serial port and Internet access to the S C Automation Customer Support Portal A serial communication cable This cable connects the computer to the LOCAL COMM PORT on the control Use a straight through cable not a null modem cable The cable must be long enough to connect to an installed IntelliCap control The serial connection is RS232 with a DB9 pin connector If the computer only...

Страница 7: ...ated voltage reduction With this wiring configuration voltage override logic will not have effective control of the primary feeder voltage Because calculations are based on single phase current balanced three phase currents or loads will produce the best results Current measurements at the time of instal lation may help to decide the best phase to monitor if the feeder is significantly unbalanced ...

Страница 8: ... Detail notes for Figure 1 1 Install the current sensor on the source side of the capacitor bank connection 2 Thecurrentsensormustbegroundedatthetopofthepole 3 A dedicated potential transformer for control power should be connected with one leg connected to the same phase as the current sensor Installation ...

Страница 9: ...g etc If a malfunction is suspected treat all components of the installation including the control and associated mounting hardware as if they were elevated to primary HIGH voltage You must follow the sequence of installation steps outlined in this instruction sheet to ensure a safe and successful control installation WARNING These instructions do NOT replace the need for utility operation standar...

Страница 10: ...r panel in a location with minimum traffic exposure All IntelliCap controls have an internal terminal strip The terminal strip wires connect to the meter base cable connector or the cable wire directly A meter base with a pole mounting bracket and a meter ring assembly is available from S C Electric Company Meter Base Mounting STEP 4 Confirm that the meter base socket is wired correctly for this c...

Страница 11: ... for capacitor controls with catalog number suffix J62 Ac line Open Ac neutral Close Current sensor neutral Current sensor hot Ac line Open Ac neutral Close Current sensor neutral Current sensor hot Figure 6 Six jaw meter base socket configuration for capacitor controls with catalog number suffix J63 Ac line Open Ac neutral Close Current sensor neutral Current sensor hot Installation ...

Страница 12: ...citor controls with catalog number suffix J65 Figure 9 Six jaw meter base socket configuration for capacitor controls with catalog number suffix J68 Ac line Open Ac neutral and current sensor neutral Close Current sensor hot alternate Current sensor hot Ac line Open Ac neutral Close Not connected Not connected Ac neutral Close Neutral sensor hot Ac line Open Neutral sensor return Installation ...

Страница 13: ...installing this control Figure 10 Grounding diagram for the IntelliCap control Voltage transformer Open Ground lug Close Ac line Ac neutral Capacitor bank switch Common neutral Installation WARNING These instructions do not replace the need for utility construction and operating standards Any conflict between the information in this document and utility standards and practices should be reviewed b...

Страница 14: ...ll a hole for the top bolt or start the top lag screw STEP 2 Support the control and install the top bolt to hold the control on the pole or hang the control on the top lag screw STEP 3 Vertically align the control on the pole and drill the bottom hole Install the bottom bolt or lag screw STEP 4 Tighten the two bolts or lag screws STEP 5 Confirm that the cable from the switch and power source is w...

Страница 15: ...nector on this control See Figure 11 on page 16 A bracket mounted control may have a d d i t i o n a l s e n s o r c a b l e c o n n e c t o r s installed on the bottom of the enclosure The con nector configuration is shown on a label inside the enclosure door STEP 4 Connect the ground lug Use the ground lug on the bottom of the enclo sure to ground the control See Figure 10 on page 13 The ground ...

Страница 16: ...ine current sensor hot Not connected Return for line neutral sensors Ac line Open Close Not connected Ac neutral IntelliCap terminal strip configuration Ac line Ac neutral Current sensor return Ground Conduit entrance Current sensor hot Open Close Figure 11 The terminal strip and connectors for a bracket mounted control Installation ...

Страница 17: ...CLOSE OPEN switch on the faceplate to operate the capacitor bank Verify visually that the faceplate LCD screen correctly indicates each bank switch position T he ba nk st atus on t he LCD screen Stat BankOff line or Stat Bank Online indicates the last requested operation which is normally the same as the present switch position The Stat display will be blank until the bank has been switched for th...

Страница 18: ...18 S C Instruction Sheet 1022 510 Wiring Diagrams ...

Страница 19: ...S C Instruction Sheet 1022 510 19 Wiring Diagrams ...

Страница 20: ...20 S C Instruction Sheet 1022 510 Wiring Diagrams ...

Страница 21: ...S C Instruction Sheet 1022 510 21 Wiring Diagrams ...

Страница 22: ...22 S C Instruction Sheet 1022 510 Wiring Diagrams ...

Страница 23: ...S C Instruction Sheet 1022 510 23 Wiring Diagrams ...

Страница 24: ...24 S C Instruction Sheet 1022 510 Wiring Diagrams ...

Отзывы: