14
S&C Instruction Sheet 1022-510
STEP 6.
Set the IntelliCap control to
Manual
operation
mode.
WARNING
The AUTO/MANUAL switch must be set to
Manual
mode to avoid unexpected operation of the capacitor
bank during installation or setup operations .
STEP 7.
Reinstall the 10-A load fuse.
T he faceplate LCD screen shou ld st a r t
scrolling through real-time and setpoint data.
See Figure 2 on page 10. If one of the following is true,
see Instruction Sheet 1022-550, “S&C IntelliCap
®
Automatic Capacitor Control:
Troubleshooting
.”
• The display is blank.
• The display reads
**RE**
,
**REA**
,
**READ**
,
or
**READY**
and does not clear.
• The display shows an error message.
Bracket Mounting
Attach the control to the pole with either lag bolts for a
wood pole, or metal straps for a concrete or metal pole. Then
connect the cables.
For a Wood Pole
Follow these steps to attach the enclosure to a wood pole:
WARNING
The control must be set to
Manual
mode to avoid
unexpected operation of the capacitor bank during
installation or setup operations .
STEP 1.
Use two 1/2-inch through-bolts or lag bolts, and flat
washers if necessary. Drill a hole for the top bolt, or
start the top lag screw.
STEP 2.
Support the control and install the top bolt to hold
the control on the pole, or hang the control on the
top lag screw.
STEP 3.
Vertically align the control on the pole and drill the
bottom hole. Install the bottom bolt, or lag screw.
STEP 4.
Tighten the two bolts or lag screws.
STEP 5.
Confirm that the cable from the switch and power
source is wired correctly for the connector on the
control. Wiring options for the connector are shown
in Figure 11 on page 16.
A bracket-mounted control may have additional
sensor-cable connectors installed on the bottom
of the enclosure. The connector configuration is
shown on a label inside the enclosure door.
STEP 6.
Connect the ground lug.
Use the ground lug on the bottom of the
enclosure to ground the control. The ground lug
will accommodate up to #2 copper or aluminum,
solid or stranded wire.
WARNING
The control must be properly grounded . You must read
and understand all applicable grounding codes and
requirements for your service area before installing this
device .
STEP 7.
Connect the cable from the junction box to the
connector on the bottom of the control.
When an energized cable is connected to the
control, after a few seconds the LCD screen will
start to scroll.
Installation
Содержание IntelliCap
Страница 18: ...18 S C Instruction Sheet 1022 510 Wiring Diagrams ...
Страница 19: ...S C Instruction Sheet 1022 510 19 Wiring Diagrams ...
Страница 20: ...20 S C Instruction Sheet 1022 510 Wiring Diagrams ...
Страница 21: ...S C Instruction Sheet 1022 510 21 Wiring Diagrams ...
Страница 22: ...22 S C Instruction Sheet 1022 510 Wiring Diagrams ...
Страница 23: ...S C Instruction Sheet 1022 510 23 Wiring Diagrams ...
Страница 24: ...24 S C Instruction Sheet 1022 510 Wiring Diagrams ...