4th Edition of TEMI880 IM : Jan. 29. 2007 Page 86 / 119
2.12.3.1 Set ON/OFF Signal
Symbol
Parameter
Setting Range
Unit
Init. Value
LSP
LOW SP
T.EU
T.EU(0%)
MSP
MIDDLE SP
T.EU
T.EU(0%)
HSP
HIGH SP
T.EU(0~100%)
TEMP RL
≤ LOW SP
< MIDDLE SP
< HIGH SP
≤ TEMP RH
T.EU
T.EU(0%)
HD
HIGH DIFFERENCE
T.EUS(0~10%)
T.EUS
T.EUS(0%)
LD
LOW DIFFERENCE
T.EUS(0~10%)
T.EUS
T.EUS(0%)
2.12.3.2 Set Inner Signal
Symbol
Parameter
Setting Range
Unit
Init. Value
RANGE-L
INNER SIGNAL
RANGE LOW
T.EU
T.EU(0%)
RANGE-H
INNER SIGNAL
RANGE HIGH
T.EU(0~100%)
RANGE-L
≤ RANGE-H
T.EU
T.EU(0%)
TIME
INNER SIGNAL
DELAY TIME
00.00~99.59
(HOUR.MIN)
ABS
00.00
ITEM
INNER SIGNAL
ITEM
TEMP, HUMI
ABS
TEMP
TYPE
INNER SIGNAL
TYPE
SP, PV, TSP
ABS
SP
BAND
INNER SIGNAL
BAND DIRECT
INB, OUTB
ABS
INB
2.12.4.1 Set PID Range
Symbol
Parameter
Setting Range
Unit
Init. Value
TEMP AT
TEMP AUTO
TUNING POINT
0.01~1.00
ABS
0.10
H.COMD
HUMIDITY
CONTROL MODE
CMD0, CMD1
ABS
CMD1
HUMI AT
HUMI AUTO
TUNING POINT
0.01~1.00
ABS
0.10
T1
TEMP REFERENCE
POINT1
DRY.L < T1 < DRY.H
ABS
(D.RL+D.RH)/2
H2
HUMI REFERENCE
POINT2
H.EU
2(H.RL+H.RH)/3
H1
HUMI REFERENCE
POINT1
H.EU(0~100%)
HUMI RL
< H1 < H2
< HUMI RH
H.EU
(H.RL+H.RH)/3
T3
TEMP REFERENCE
POINT3
T.EU
2(T.RL+T.RH)/3
T2
TEMP REFERENCE
POINT2
T.EU(0~100%)
TEMP RL
< T2 < T3
< TEMP RH
T.EU
(T.RL+T.RH)/3