62
2
1
[Fig. 7-8] Time signal setting #2
[Fig. 7-9] Time signal setting #3
Parameter
Initial value
Setting range
Unit
Delay time
Operation time
000.00.00(OFF)~999.59.59 (Hour, Min, Sec)
000.00.00(OFF)~999.59.59 (Hour, Min, Sec)
ABS
ABS
000.00.00
000.00.00
(2) Time signal time setting operation
● The time signal 2~17 (TS2~17) operate depending on delay time and operation time.
The time signal is “ON” after setting time is elapsed in delay time from
the corresponding segment starting point.
●
However, the time signal is not operated when the corresponding
segment time is bigger than delay time.
The time signal is “ON” by the delay time in corresponding segment
is “ON” only for set time in operation time. .
●
However, the time signal is “ON” for the corresponding segment operation
when the (delay time + operation time) is bigger than corresponding
segment time and it is not operated in the next segment.