98
98
17-3. Serial communication environment setting
ԙ
This is the screen where you can set the communication conditions such as communication protocol and speed.
[Fig. 17-4] Communication environment setting screen(RS232C/485)
1
2
5
7
3
6
4
①
Setting the communication protocol.
②
Setting the communication speed
●
Refer to [Fig. 17-5]
③
Setting the stop bit
④
Setting the data length
●
The data length is fixed in 7 when the communication protocol is
set in MODBUS ASC.
●
The data length is fixed in 8 when the communication protocol is
set in MODBUS RTU.
⑤
Setting the parity
●
NONE : No parity
●
EVEN : Even number parity
●
ODD : Odd number parity
⑥
Other parameter settings
●
Communication address : In case of RS485 communication, up to
99 addresses can be assigned differently.
●
Response time : Set the response time
⑦
Used to apply the contents after changing serial communication
settings
●
Press the button to display the system restart selection screen
Refer to [Fig. 17-6]
Содержание SDR100E Series
Страница 19: ...17 02 Operation and setting Password input screen Screen without DI option Screen with DI option...
Страница 23: ...Main screen Part 03...
Страница 25: ...4 1 Graph recording screen 24 Graph recording setting Part 04...
Страница 36: ...5 1 Graph view 35 5 2 Data searching 36 Graph searching Part 05...
Страница 39: ...Function setting Part 06...
Страница 51: ...Part 08 Setting canned message...
Страница 53: ...Setting reserve operation Part 09...
Страница 64: ...Part 11 Error history display...
Страница 68: ...Part 12 Setting system parameter...
Страница 70: ...13 1 Sensor input screen 69 Screen for setting the sensor input Part 13...
Страница 95: ...DI function and operation Part 16...
Страница 102: ...System initial setting9 Part 18...
Страница 106: ...104 Fig 18 8 Screen setting for sending to SDR100 Upload Fig 18 9 Screen for parameter file selection to send to SDR100...