Sym
Parameter
Setting Range
Unit
Initial
Remark
ALT1
Alarm Type 1
Refer to (Table 3 : Type of Alarm)
ABS
AH.F
All time
indicate
AL-1
Set value of
ALT1
EU(-100.0∼100.0%)
EU
EU(100.0%)
Not
deviation
alarm
AL1.H
Upper-Limit of
set value ALT1
EUS(-100.0∼100.0%)
EUS
EUS(0.0%)
Deviation
alarm
AL1.L
Lower-Limit of
set value ALT1
EUS(-100.0∼100.0%)
EUS
EUS(0.0%)
Deviation
alarm
A1DB Alarm Type1 DB
EUS(0.0∼100.0%)
EUS
EUS(0.5%)
All time
indicate
A1DY
Delay Time of
Alarm 1
0.00∼99.59 (MM:SS)
MM.SS
0.00
All time
indicate
ALT2
Alarm Type 2
Refer to (Table 3 : Type of Alarm)
ABS
AH.F
All time
indicate
AL-2
Set value of
ALT2
EU(-100.0∼100.0%)
EU
EU(100.0%)
Not
deviation
alarm
AL2.H
Upper-Limit of
set value ALT2
EUS(-100.0∼100.0%)
EUS
EUS(0.0%)
Deviation
alarm
AL2.L
Lower-Limit of
set value ALT2
EUS(-100.0∼100.0%)
EUS
EUS(0.0%)
Deviation
alarm
A2DB Alarm Type2 DB
EUS(0.0∼100.0%)
EUS
EUS(0.5%)
All time
indicate
A2DY
Delay Time of
Alarm 2
0.00∼99.59 (MM:SS)
MM.SS
0.00
All time
indicate
ALT3
Alarm Type 3
Refer to (Table 3 : Type of Alarm)
ABS
AH.F
All time
indicate
AL-3
Set value of
ALT3
EU(-100.0∼100.0%)
EU
EU(100.0%)
Not
deviation
alarm
AL3.H
Upper-Limit of
set value ALT3
EUS(-100.0∼100.0%)
EUS
EUS(0.0%)
Deviation
alarm
AL3.L
Lower-Limit of
set value ALT3
EUS(-100.0∼100.0%)
EUS
EUS(0.0%)
Deviation
alarm
A3DB Alarm Type3 DB
EUS(0.0∼100.0%)
EUS
EUS(0.5%)
All time
indicate
A3DY
Delay Time of
Alarm 3
0.00∼99.59 (MM:SS)
MM.SS
0.00
All time
indicate