The parameter to select type of temperature unit for ℃ or ℉.
Its initial selection is ℃ type.
Refer to Table 1 when change temperature unit.
The parameter to set High-Limit for input temperature measuring range.
The parameter to set Low-Limit for input temperature measuring range.
The parameter to set the position of decimal value in case that sensor type is
mV or V. The position if decimal value can change 0 ~ 3.
its initial set value is ‘1’.
The parameter to set High-Limit of input measuring scale in case that sensor
type is mV or V.
its initial value of ‘In.SH’ is ‘100.0’
The parameter to set Low-Limit of input measuring scale in case that sensor
type is mV or V.
its initial value of ‘In.SL’ is ‘0.0’
The parameter to set PV filter for stabilizing from electromagnetic noise etc.
it may effect violation of PV value. Its initial value of ‘In. FL’ is OFF and
can change 1 sec to 120 sec.
The parameter to set a direction of PV operation when sensor open. When set
value of BSL is ‘UP’, PV operation is for High-Limit of Input Sensor.
When set value of BSL is ‘DOWN’, PV operation is for Low-Limit of Input
Sensor. Its initial setting is ‘UP’ (* in case of mV, V input, initialize ‘OFF’ and
No checking Sensor-Open in 10V, 20mV, 100mV
The parameter to set whether using RJC or not in case that input sensor is
thermocouple. Its initial setting of ‘rSL’ is ‘ON’
The parameter to set range of Bias in PV value enabling Bias process.
Bias range can set Max 4. for further information, refer to Fig 1. and Fig 2.
The parameter to set Bias value of PV in Bias range.
For further information, refer to Fig 1. and Fig 2.
The parameter to set for decreasing when PV is unstable due to senstive
sensor response under normal control.
...
...