2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 128 / 176
17.1.3 Segment alarming signal setting screen
▶
This is the screen for setting SEG alarming.
▶
8 alarms can be set.
▶
SEG alarming signal operation is carried out according to the setting in the alarming type, the types of
alarming amounts to 20.
Table 17-3. SEG alarming signal setting screen
Parameter
Setting range
Unit
Initial data
SEG alarming #n
type
Non-use, AH.F, AL.F, DH.F
DL.F, DH.R, DL.R
DO.F, DI.F, AH.R, AL.R
ABS
Non-use
SEG alarming #n
POINT
EU(-5.0~105.0%)
EU
EU(100.0%)
(alarming #n type =
not DO.F, DI.F,
DO.FS, and DI.FS)
SEG alarming #n
upper limit POINT
EUS
SEG alarming #n
lower limit POINT
EUS(-100.0~100.0%)
EUS
EUS(0.0%)
(alarming #n type =
not DO.F, DI.F, DO.FS
and DI.FS)
SEG alarming #n
hysteresis
EUS(0.0~100.0%)
EUS
EUS(0.5%)
SEG alarming #n
delay time
0.00~99.59 (MIN.SEC)
ABS
00.00
* #n : 1 ~ 8
[Fig. 17-5] SEG alarming signal setting screen