2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 100 / 176
12.1.2.1 Operation Direction
12.1.2.2 Output Cycle
▶
Applies only when control output type is “SSR(Solid State Relay)”.
▶
It refers one cycle of ON/OFF at setup time.
▶
“SSR” with output cycle is 10 second.
0%
Deviation (PV-SP)
-
+
Control Output (MV)
100%
Control Output increase when PV is smaller
than SP. → Heating, Humidify
Control Output increase when PV is bigger
than SP. → Cooling, Dehumidify
Reverse
Forward
Control output (MV) = 50%
10sec
5 sec 5sec
OFF
ON
Control output (MV) = 70%
10sec
7sec 3sec
OFF
ON
Control output (MV) = 30%
10sec
3sec 7sec
OFF
ON