Troubleshooting
12-2-10 O.C.(Over Current) error
1. Checklist :
1) Is the Shunt resistance value correct?
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
Is the O.C.(Over Current) error occurred?
Is the Shunt resistance value normal?
Is the interphase resistance value
of compressor (u
↔
v, v
↔
w, w
↔
u) normal?
Is the compressor body and
interphase resistance insulated?
Is the condition of
indoor/outdoor temperature normal load?
Is the position of temperature sensor
and the sensing value normal?
Is the connection cable for
the compressor and power terminal normal?
Exchange the PCB.
Terminate the service.
Exchange the PCB.
Exchange the Compressor.
Exchange the Compressor.
Restart after returning
to the normal load.
Correct the sensor position or
exchange the sensor.
Correct the cable connection.
Is the O.C. error occurred again?
Terminate
the service.
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Yes
No
No
Yes
No
25890A(1)_1.indd 12
2006-04-14 ソタネト 2:23:57
Содержание UH052EAV
Страница 36: ...MEMO Samsung Electronics 5 4 ...
Страница 68: ...Samsung Electronics 7 3 This Document can not be used without Samsung s authorization UH070EAV Wiring Diagram ...
Страница 70: ...Samsung Electronics 8 2 Outdoor Unit This Document can not be used without Samsung s authorization 8 2 ...
Страница 104: ...Samsung Electronics OUTDOOR FAN B D DIODE IPM DC_LINK CAP SMPS IGBT 13 3 UH052EAV Block Diagram ...
Страница 105: ...13 4 Samsung Electronics UH070EAV OUTDOOR FAN IGBT DIODE IPM DC_LINK CAP SMPS B D Block Diagram ...
Страница 115: ...14 10 Samsung Electronics MEMO ...