Operating Instructions and Installation
Samsung Electronics
12-5
Troubleshooting
12-2-4 In case of heating at the cooling mode or cooling at the heating mode
1. Troubleshooting procedure
Change the setting temperature of
remote control.
Operate it with a heating mode
as soon as the defrosting is finished.
After 3 minutes, cooling
and heating start automatically.
No
No
No
Yes
Yes
Yes
Is the Thermo off?
Is the unit
in the defrosting operation?
Is the compressor
in 3 minutes off?
Check the resistance value
of 4-WAY valve coil.
Go to the next page
4-WAY valve main body error
Attach the
sensor correctly.
Over shortage
of the refrigerant
Connect the connecter
correctly.
4-WAY valve coil error
Exchange
the outdoor PCB.
No
Yes
Yes
Yes
OK
Yes
No
No
No
NG
No
Is much frost
in the indoor heat
exchanger?
Does the
4-WAY valve operate
normally?
Is the
outdoor air sensor and
outdoor heat exchanger attached
correctly?
Is the
4-WAY valve connector
connected correctly?
Dose the
voltage of AC 220V
apply to the connector of 4-WAY
valve coil during the
operation?
25890A(1)_1.indd 5
2006-04-14 ソタネト 2:23:54
Содержание UH052EAV
Страница 36: ...MEMO Samsung Electronics 5 4 ...
Страница 68: ...Samsung Electronics 7 3 This Document can not be used without Samsung s authorization UH070EAV Wiring Diagram ...
Страница 70: ...Samsung Electronics 8 2 Outdoor Unit This Document can not be used without Samsung s authorization 8 2 ...
Страница 104: ...Samsung Electronics OUTDOOR FAN B D DIODE IPM DC_LINK CAP SMPS IGBT 13 3 UH052EAV Block Diagram ...
Страница 105: ...13 4 Samsung Electronics UH070EAV OUTDOOR FAN IGBT DIODE IPM DC_LINK CAP SMPS B D Block Diagram ...
Страница 115: ...14 10 Samsung Electronics MEMO ...