E-
3
EN
G
LI
SH
Safety Precautions
The following safety precautions must be taken when installing the unit.
R410A refrigerant is used for MINI DVM air conditioner.
- When using R410A, moisture or foreign substances may affect to the capacity and reliability of
the product. Safety precautions must be taken when installing the refrigerant pipe.
- The design pressure of the unit is 4.1MPa. Select appropriate material and thickness according
to the regulations.
- R410A is a quasi-azeotrope of two refrigerants.
Make sure to charge liquid one when adding refrigerant.
If you charge gaseous refrigerant, it may affect the capacity and reliability of the product as
a result of change formation of the refrigerant.
Connect only the indoor units fit on R410A refrigerant. Check whether the indoor units can be
connected with the product’s catalogue.
(When incorrect indoor units are connected, they cannot operate normally.)