49
ENGLISH
Main
menu
Sub
menu
Function
Data
bit
Factory
setting
Description
Unit
1
1
Wireless remote controller
Option setting/checking (1)
Cooling/Heating selection
1
0
0 – Cooling/Heating,
1 – Cooling only
-
Use of wireless remote controller
2
1
0 – No use, 0 - Use
-
MAIN/SUB wired remote
controller
3
0
0 –MAIN, 1- SUB
-
Temperature unit
4
0
0 – Celcius(°C), 1 – Fahrenheit(°F)
-
2
Wireless remote controller
Option setting/checking (2)
Temperature sensor selection
1
0
0 – Indoor unit,
1 – Wired remote controller
-
Use of average temperature
2
0
0 – No use, 0 - Use
-
Use of Auto mode
3
1
0 – No use, 0 - Use
-
Temperature display
4
0
0 – Set temperature,
1 - Room temperature
-
AC On/Off button function
5
0
0 – Indoor unit + ERV,
1 – Indoor unit only,
2 – ERV only,
-
3
Blade
setting/checking
Lock of Blade1
1
0
0 – Unlock, 1 – lock
-
Lock of Blade2
2
0
0 – Unlock, 1 – lock
-
Lock of Blade3
3
0
0 – Unlock, 1 – lock
-
Lock of Blade4
4
0
0 – Unlock, 1 – lock
-
4
ERV option
Setting/checking
Use of By-Pass mode
1
0
0 – No use, 1 - Use
-
Use of Auto mode
2
0
0 – No use, 1 - Use
-
Use of air purification mode
3
0
0 – No use, 1 - Use
-
Use of external control
4
0
0 – No use, 1 - Use
-
5
Room Temperature
compensation
Temperature control reference 1,2,3
0
-9 ~ 40(°C)
0.1(°C)
Temperature compensation value
4,5,6
0
-9.9 ~ 9.9(°C)
0.1(°C)
6
Number of connected units
Number of indoor units
1,2
-
0 ~ 16
-
Number of ERVs
3,4
-
0 ~ 16
-
7
Temperature increment/decrement (°C only)
1
0
0-1°C, 1-0.5°C, 2-0.1°C
-
0
Factory option setting
1
0
0 – Unchanged
1 – Factory setting
-
2
1
Software code
1~6
-
Software code
-
2
Software version
1~6
-
Software version
-
3
1
Indoor unit room temperature
1,2,3
-
Room temperature
°C
2
Indoor unit EVA IN temperature
1,2,3
-
EVA IN temperature
°C
3
Indoor unit EVA OUT temperature
1,2,3
-
EVA OUT temperature
°C
4
Indoor unit EEV step
1,2,3
-
EEV step
-
5
Indoor unit option checking (1)
Use of central control
1
-
0 – No use, 1 - Use
-
Use of drain pump
2
-
0 – No use, 1 - Use
-
Use of electric heater
3
-
0 – No use, 1 - Use
-
Use of hot water coil
4
-
0 – No use, 1 - Use
-
6
Indoor unit option checking (2)
Use of external control
1
-
0 – No use, 1 - Use
-
Use of RPM compensation
2
-
0 – No use, 1 - Use
-
Filter time
3
-
0 – 2000 hours, 1 – 1000 hours
-
Heating temperature
compensation
4
-
0-2°C, 1-5°C
-
EEV stop step in heating
5
-
0 – 1/80 steps, 1 – 80
-