14
3 8 N C
RY75
RY76
RY77
1 8 N C
1(L) 1(N)
Control-KIT Connections
Vd
Vd
TR
TR TEI TEI
V1
V2
F3
F4
F1
F2
TEO TEO
COM
HP
CO AV
OV
Outdoor unit
Wired remote control
F3 : Wired remote control commnunication cable
F4 : Wired remote control commnunication cable
F1 : Outdoor unit communication cable
F2 : Outdoor unit communication cable
Evap Room
Sensor
Defrost signal
(220-240V)
Evap In
Sensor
Evap Out
Sensor
Simple BMS
INSTALLATION
(Continued)
220~240V,
Power supply
220~240V,
AHU fan ON contact signal
Fan status feedback
(Non-voltage contact signal)
POWER[AC] FAN ON[AC] FAN CHECK
1(L) 1(N)
Brazing the Pipe
• Make sure that there is no moisture inside the pipe.
• Make sure that there are no foreign materials and impurities in the pipe.
• Make sure that there is no leak.
• Be sure to follow the instruction when brazing the pipe.
1) Use Nitrogen gas when brazing the pipes as shown
in the picture.
2) If you do not use Nitrogen gas when brazing the
pipes, oxide may form inside the pipe. It can cause
the damage of the compressor, valves.
3) Adjust the flow rate of the Nitrogen gas with a
pressure regulator to maintain 0.05m3/h or less.
Brazing part
Nitrogen gas
1/4" copper pipe
Stop valve
Taping
Pressure regulator
Flowmeter
The use of Nitrogen gas
NASA PJT_AHU Kit_MXD-K@@@AN Series_EN_03711A(1).indd 14
2013-01-11 오후 3:20:26
Содержание MXD-K025AN
Страница 1: ...NASA PJT_AHU Kit_MXD K AN Series_EN_03711A 1 indd 40 2013 01 11 오후 3 20 36 ...
Страница 38: ...37 MEMO NASA PJT_AHU Kit_MXD K AN Series_EN_03711A 1 indd 37 2013 01 11 오후 3 20 36 ...
Страница 39: ...38 MEMO NASA PJT_AHU Kit_MXD K AN Series_EN_03711A 1 indd 38 2013 01 11 오후 3 20 36 ...
Страница 40: ...39 MEMO NASA PJT_AHU Kit_MXD K AN Series_EN_03711A 1 indd 39 2013 01 11 오후 3 20 36 ...