Содержание MWR-WW00

Страница 1: ...DVM Hydro Unit_MWR WW00_IM_EN_03647A 1 indd 26 2013 01 09 오후 2 48 45 ...

Страница 2: ... imagine the possibilities ThankyouforpurchasingthisSamsungproduct To receive more complete service please register your product at www samsung com register DB68 03647A 1 AR EN ES FR IT PT DE EL RU DVM Hydro Unit_MWR WW00_IM_EN_03647A 1 indd 27 2013 01 09 오후 2 48 45 ...

Страница 3: ...o so may result in product malfunction electric shock and fire When you need to repair the product you should contact a service center All the electric work should be performed in accordance with local regulation and installation manual by a certified technician f f Failure to do so may result in product malfunction electric shock and fire due to defect Install the product on a hard and even surfa...

Страница 4: ...mage Do not install the product in specific areas exposed to oil or vapor f f Failure to do so may result in part damage or abnormal operation Do not put undue stress on the power cable f f Failure to do so may result in broken cable and fire Do not install the product in areas where acid or alkali liquid or special spray are used f f Failure to do so may result in electric shock or abnormal opera...

Страница 5: ...a certified technician Check and confirm the power is off before installing your wired remote controller Install the wired remote controller cables in accordance with the electrical wiring regulation and allow it to pass through the inner area of the wall so that other people can t reach it CAUTION External Dimensions 120 4 72 124 4 88 63 8 2 51 19 5 0 76 Unit mm inch DVM Hydro Unit_MWR WW00_IM_EN...

Страница 6: ...wdriver into the square groove in the upper area of the hook to disassemble it easily NOTE 2 Arrange the power cable and the communication cable so that they fit in the housing along the edges of the rear cover If you need more space for the wiring work you can take it off 15cm 5 90 When the cable is not concealed When the cable is concealed 10cm 3 93 DVM Hydro Unit_MWR WW00_IM_EN_03647A 1 indd 5 ...

Страница 7: ...nt cover Wired remote controller Hydro Unit Hydro Unit PCB Before fixing the rear cover allow at least 10mm 0 4 inch space of upper side left side right side and 50mm 2inch space of bottom side You must fit the screws into the screw holes Do not tighten the screws on the PCB terminal with excessive force 4 Reassemble your wired remote controller Align the controller with the upper groove first and...

Страница 8: ...d remote controller by using four pieces of PVC wire remove the 30cm 12inch of the sheath of the cable and install it only with the four pieces of wires Recommended specification AWG21 The followings are the specs of the compressed ring terminal connectable to your wired remote controller PCB Range of Permitted Wires Rated Size Stud Size Basic Size mm AWG mm2 mm2 mm t øD G E F W L 22 16 0 25 1 65 ...

Страница 9: ...buttons at the same time for more than 5 seconds f f The system will reset and tracking will start again 3 During the tracking the total number of currently searched Hydro Unit will be displayed If you want to do system reset for your wired remote controller press the Esc and Delete buttons at the same time for more than 5 seconds Only the master wired remote controller can display the total numbe...

Страница 10: ...it COM1 F1 F2 COM2 F3 F4 COM2 F3 F4 COM2 F3 F4 COM1 F1 F2 Hydro Unit Wired remote controller Wired remote controller Wired remote controller Hydro Unit Hydro Unit Regardless of the Hydro Unit group address RMC address setting only the Hydro Unit connected to COM2 is individually controlled The power cable V1 V2 is not connected between Hydro Units CAUTION DVM Hydro Unit_MWR WW00_IM_EN_03647A 1 ind...

Страница 11: ...g one wired remote controller to control Hydro Units connected to different outdoor unit Outdoor unit Outdoor unit COM1 F1 F2 COM1 F1 F2 COM2 F3 F4 COM2 F3 F4 Hydro Unit Hydro Unit Wired remote controller Regardless of the Hydro Unit group address RMC address only the Hydro Units connected to COM2 are controlled in group The power cable V1 V2 is not connected between Hydro Units The power cable fo...

Страница 12: ... sensor use please install the master remote controller at indoor places Outdoor unit Wired remote controller Slave COM1 F1 F2 COM2 F3 F4 Hydro Unit Wired remote controller Master For the slave wired remote controller settings please refer to the sections about the wired remote controller installation service mode Refer to page17 0 Master 1 Slave CAUTION DVM Hydro Unit_MWR WW00_IM_EN_03647A 1 indd...

Страница 13: ... the Esc and Delete buttons at the same time for more than 5 seconds f f The communication of your wired remote controller will be initialized and the device will search for the Hydro Unit connected to your wired remote controller again DVM Hydro Unit_MWR WW00_IM_EN_03647A 1 indd 12 2013 01 09 오후 2 48 42 ...

Страница 14: ...he address of error A In and the error code will be displayed alternately on the remote controller display 2 Outdoor unit error f f The address of error A Out and error code will be displayed alternately on the remote controller display 3 Wired remote controller error f f The error code will blink at 0 5 second interval on the remote controller display and the address of error will not be displaye...

Страница 15: ...n Error on EVA IN sensor of Hydro unit Short or Open Error on EVA OUT sensor of Hydro unit Short or Open EVA IN sensor of Hydro unit is detached EVA OUT sensor of Hydro unit is detached EVA IN and EVA OUT sensor of Hydro unit is detached Error due to opened EEV of Hydro unit 2nd detection Error due to closed EEV of Hydro unit 2nd detection Mixed operation mode error EEPROM error EEPROM option sett...

Страница 16: ...r on water tank sensor Short or open Error due to pipe rupture protection Error due to freeze prevention Water temperature sensor on water outlet pipe is detached Flow switch off error When the switch is turned off within 10 seconds after a pump starts its operation Error due to incorrect thermostat connection DVM Hydro Unit_MWR WW00_IM_EN_03647A 1 indd 15 2013 01 09 오후 2 48 43 ...

Страница 17: ... screen f f Using the buttons select a sub menu number and press the button to enter data setting screen f f When you enter the setting stage the current setting value will be displayed f f Refer to the chart for data settings f f Using the buttons change the setting value Press the button to move to the next setting value f f Press the Set button to save the setting value and exit to the sub menu...

Страница 18: ... controller set check Checking current sensor temperature value 123 0 9 40 C 15 8 104 F 4 Setting compensation temperature value 123 0 9 9 9 9 C 14 18 49 82 F 0 1 C 32 18 F 5 Checking the number of connected devices The number of connected devices 12 0 16 1 6 Setting desired temperature unit Available only when the temperature display is C 1 1 0 1 C 33 8 F 1 0 5 C 32 9 F 2 0 1 C 32 18 F 0 Reset to...

Страница 19: ...tting screen f f When you enter the setting stage the current setting value will be displayed f f Refer to the chart for data settings f f Using the buttons change the setting value Press the button to move to the next setting value f f Press the Set button to save the setting value and exit to the sub menu setting screen f f Press the ESC button to exit to normal mode When setting the data you ca...

Страница 20: ...00 2099 Year 2 Current time setting month date 12 34 01 01 1 12 1 31 Month Date 3 Current time setting day hour minute Day AM PM 24 12 34 Fri PM 12 00 Sun Sat AM PM 0 12 0 60 Day hour minute 3 1 Summer time use and setting methods Use of summer time Y N 1 0 0 Disuse 1 Use Summer time application method 2 0 0 Weekly 1 Daily 2 Summer time use weekly Start month th Sunday 12 4 03 F Jan Dec month 1 4 ...

Страница 21: ...uttons select a sub menu number and press the button to enter data setting screen f f When you enter the setting stage the current setting value will be displayed f f Refer to the chart for data settings f f Using the buttons change the setting value Press the button to move to the next setting value f f Press the Set button to save the setting value and exit to the sub menu setting screen f f Pre...

Страница 22: ...0 40 1 C Water Law Auto heating ambient temperature Max 2011 10 20 5 1 C Min 2012 15 10 20 1 C Temperature of auto heating discharge water WL1 Floor Max 2021 45 35 55 1 C Min 2022 30 17 37 1 C Temperature of auto heating discharge water WL2 FCU Max 2031 50 35 55 1 C Min 2032 35 17 37 1 C Auto heating of wired remote controller WL type 2041 1 WL1 1 2 Use of thermostat 1 Floor 2091 0 No 0 1 Yes 2 FC...

Страница 23: ... Hot water 0 1 Heating Heating priority 4012 0 15 20 1 C Heating Off 4013 35 14 35 1 C Overshoot 4014 2 1 4 1 C Others Outing mode Temperature of cooling water oulet 5011 25 5 25 1 C RoomTemperature of cooling Mode 5012 30 18 30 1 C Temperature of heating discharge water 5013 15 15 55 1 C Indoor heating temperature 5014 16 16 30 1 C Temperature of auto heating WL1 water 5017 15 15 55 1 C Temperatu...

Страница 24: ...can check the setting value of the field setting address as follows f f Using the buttons move to the field specification address you want to check f f Using the button move to the next address f f Using the button move to the previous address f f Press the ESC button to exit to normal mode When you don t enter any buttons for more than 3 minutes you will be back to normal mode NOTE DVM Hydro Unit...

Страница 25: ...stallation service mode 2 When using the self test mode of the wired remote controller press the and buttons for more than 3 seconds 3 You can operate the self test mode as follows f f Load list When pressing the corresponding button you can set the load On or Off Enter button Operating part LCD display Water pump Booster heater DHW valve 2 way valve DVM Hydro Unit_MWR WW00_IM_EN_03647A 1 indd 24 ...

Страница 26: ... you don t press the Timer button for 5 seconds the previous status will be shown f f For the sensor fault or absence of sensor installation corresponding sensor temperature will be displayed as Er f f When you press the button that does not have a function will blink for 3 seconds f f When pressing the Delete button one time all the loads will be Off f f When all the loads are OFF status Cancel K...