Feature & Operation
Samsung Electronics
78
6-1-7 Indoor fan control in the Heating Mode
Indoor fan is controlled depending on the temperature of indoor heat exchanger in the heating mode.
●
Indoor fan control
The temperature of indoor heat exchanger
Indoor fan speed
below 28°C
off
28°C ~ below 34°C
LL speed
34°C ~ below 40°C
L speed
above 40°C
setting speed
When compressor is on
40°C
34°C
28°C
20°C
Setting speed
L Speed
LL Speed
OFF
Compressor
OFF
OFF
UL
ON
When compressor is off
◆
When compressor begins operating
The temperature of indoor heat exchanger
Indoor fan speed
above 20°C
UL speed
below 20°C
off
after 10 minutes when compressor stops operating
off
◆
When compressor stops operating