Drain hose installation
Testing the drainage
Prepare a little water about 5 liter.
1
Open the cover of water supply intake by turning and pulling the cover.
(MH
FEEA)
2
Pour water into the the indoor unit as shown in figure.
Note
If you do not pour water inside the water supply intake,
wateray spill from the indoor unit.
3
Confirm that the water flows out through the drain hose.
4
Reassemble the cover of water supply intake.(MH
FEEA)
H
SI
L
G
N
E
CAUTION
Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be allowed
to hang loose from its connection to the unit. Fasten the
hose to a wall, frame or other support as close to the unit as
possible.
Upward gradient
Ceiling
Support pieces
Ceiling
When not installing the drain pump
Do not give the hose upward gradient after the connection
port. This will cause water to flow backwards when the unit
is stopped, resulting in water leaks.
When installing the drain pump
The maximum height of drain pump hose is 75cm or less.
If it is raised higher than 75cm, there can be water leaks.
75cm or less
Ceiling
Water supply intake
MH
FEEA
MH
FUEA