23
K4 Switch (Electronic Valve Manual Control)
X
According to the push time of K4 Switch, A_C, A_H, …, F_C, F_H, Liquid bypass solenoid valve opens in order.
X
In Electronic Valve Manual Control mode, valve operates by K4 Push time irrespective of indoor operation mode.
X
In Electronic Valve Manual Control mode, push K1 Switch makes DATA DISPLAY MODE to start and valves will operate
following indoor operation mode.
K4
(Push time)
Display Contents
Display segment
1
2
3
4
1
A_C sol valve ON, other sol valve Off
P
A
1
0
2
A_H sol valve ON, other sol valve Off
P
A
0
1
3
B_C sol valve ON, other sol valve Off
P
B
1
0
4
B_H sol valve ON, other sol valve Off
P
B
0
1
5
C_C sol valve ON, other sol valve Off
P
C
1
0
6
C_H sol valve ON, other sol valve Off
P
C
0
1
7
D_C sol valve ON, other sol valve Off
P
D
1
0
8
D_H sol valve ON, other sol valve Off
P
D
0
1
9
E_C sol valve ON, other sol valve Off
P
E
1
0
10
E_H sol valve ON, other sol valve Off
P
E
0
1
11
F_C sol valve ON, other sol valve Off
P
F
1
0
12
F_H sol valve ON, other sol valve Off
P
F
0
1
13
Liquid b/p sol valve ON, other sol valve Off
P
S
1
0
14
sol valve Manual Control MODE end
P
Communication DATA Display
K2
(Pushed time)
Display Contents
Display segment
Remarks
1
2
3
4
1
Indoor unit main address for matching with port A
A
-
0
0
Indoor unit main address of port A : 0
2
Indoor unit main address for matching with port B
B
-
0
3
Indoor unit main address of port B : 3
3
Indoor unit main address for matching with port C
C
-
0
6
Indoor unit main address of port C : 6
4
Indoor unit main address for matching with port D
D
-
0
9
Indoor unit main address of port D : 9
5
Indoor unit main address for matching with port E
E
-
1
1
Indoor unit main address of port E : 11
6
Indoor unit main address for matching with port F
F
-
1
5
Indoor unit main address of port F : 15
7
End of K2 display
K1
(Pushed time)
Display Contents
Display segment
Remarks
1
2
3
4
11
On/Off for solenoid valve A_C, A_H
A
-
•
✴
_C : Cooling solenid valve of port
✴
•
✴
_H : Heating solenid valve of port
✴
• 3rd segment : Cooling solenid valve On : 1 / Off : 0
• 4th segment : Heating solenoid valve On : 1 / Off : 0
12
On/Off for solenoid valve B_C, B_H
B
13
On/Off for solenoid valve C_C, C_H
C
14
On/Off for solenoid valve D_C, D_H
D
15
On/Off for solenoid valve E_C, E_H
E
16
On/Off for solenoid valve F_C, F_H
F
17
On/Off for liquid by pass solenoid valve
G
Blank
0
N
Ex) On
0
F
F
Ex) Off
18
Version
8
A
2
0
Ex) October 20, 2008
p
8A 20
19
End of K1 display