22
Option
SEG7
SEG8
SEG9
SEG10
Explanation
PAGE
(When setting SEG3)
Standard for mode
changing Cooling
→
Heating mode
(When setting SEG3)
Time required for
mode change
Compensation option for Long pipe or height
diffference between indoor units
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication
Details
Indication
Details
1
0
1
0
5 min.
0
Use default value
1
1.5
1
7 min.
1
1) Height difference
1)
is more than
30m or
2) Distance
2)
is longer than 110m
2
2
2
9 min.
3
2.5
3
11 min.
4
3
4
13 min.
2
1) Height difference
1)
is 15~30m or
2) Distance
2)
is 50~110m
5
3.5
5
15 min.
6
4
6
20 min.
7
4.5
7
30 min.
K1
(Pushed time)
Display Contents
Display segment
Remarks
1
2
3
4
1
MCU address
0
Blank
0
0
MCU address 0
Blank
0
1
MCU address 1
Blank
0
2
MCU address 2
Blank
1
1
MCU address 11
Blank
1
5
MCU address 15
2
Mode switching EEV1 step
1
4
8
0
Ex) 480 steps
3
Mode switching EEV2 step
2
4
8
0
Ex) 480 steps
4
Mode switching EEV3 step
3
4
8
0
Ex) 480 steps
5
Mode switching EEV4 step
4
4
8
0
Ex) 480 steps
6
Mode switching EEV5 step
5
4
8
0
Ex) 480 steps
7
Mode switching EEV6 step
6
4
8
0
Ex) 480 steps
8
Subcooler EEV step
7
4
8
0
Ex) 480 steps
9
Subcooler-in sensor temperature
8
-
0
1
Ex) -1°C
Blank
1
0
Ex) 10°C
10
Subcooler-out sensor temperature
9
-
0
1
Ex) -1°C
Blank
1
0
Ex) 10°C
Key operation
K1
K2
K3
K4
Display MCU status
Display indoor unit's address
EEV valve passive control
Wiring works
Содержание MCU Series