11
1. MCU
specification
Installing the unit
Model
MCU-S6NEK2N
MCU-S4NEK3N
MCU-S2NEK2N
MCU-S1NEK1N
Exterior of MCU
Number of connectable indoor
units at one port
Up to 8 units
Up to 8 units
Up to 8 units
Up to 8 units
Maximum number of indoor units (Total)
8
16
32
32
The maximum capacity of the
connectable indoor units at one port
16 kW
(54MBH)
16 kW
(54MBH)
16 kW
(54MBH)
16 kW
(54MBH)
The maximum capacity of the connectable
indoor units at one port (with Y-JOINT)
32.0 kw
(108 MBH)
32.0 kw
(108 MBH)
32.0 kw
(108 MBH)
-
The maximum capacity of the
connectable indoor units
61.6 kW
(216MBH)
61.6 kW
(216MBH)
32.0 kW
(108MBH)
16 kW
(54MBH)
Internal EEV
Not included
Cannot connect indoor unit without internal EEV
2. Installing the indoor unis
Model
MCU-S6NEK2N
MCU-S4NEK3N
MCU-S2NEK2N
MCU-S1NEK1N
Example
installing
(Each port
connection)
Example
installing
(MCU series
connection)
MCU
MCU
Installing
indoor units
Under 16.0 kW indoor unit : Don’t use Y-connector
16.0 kW ~ 28.0 kW indoor unit : Use Y-connector at the Gas & Liquid line
If you want to continuous cooling operation under -5 °C, set outdoor ‘Expand operational temperature range for cooling
operation (HR only)’, and use Y-connector on 5.0 ~ 16 kW indoor unit
In case of using Y-connector, it is only connectable for port combination at below Connectable port combination for
Y-connector : A + B port, C + D port, E + F port
Non-connectable port combination for Y-connector : B + C port, D + E port, non-continuous port
Set Dip Switch option for using Y-connector
1
ON
2 3 4
1
ON
2 3 4
1
ON
2 3 4
1
ON
2 3 4
S/W Option
S/W Option
S/W Option
S/W Option
Default
Combination of A+B port Combination of C+D port Combination of E+F port
In case of MCU connection in series, the maximum capacity of indoor units
in MCU series connection is 61.6 kW
MCU series connection