8. System configuration
Installer reference guide / Mono tank integrated type
141
6) Solar Panel/DHW Thermostat, Direction of 3Way Valve, Energy Metering (#306*-308*)
Main Menu
(FSV)
Sub Menu Function
Description
FSV Step
Unit
Default
Min.
Max.
DHW
FSV 30**
Solar Panel/DHW
Thermostat
H/P Combination
3061
1
-
0 (No)
0
2
Direction of
3Way Valve
DHW Tank
3071
-
-
0
(Room)
0
1
(Tank)
Energy Metering
BUH 1 step capacity
3081
1
kW
2
1
6
BUH 2 step capacity
3082
1
kW
2
0
6
BSH capacity
3083
1
kW
3
1
6
• #3061 : Solar panel application (Not supported)
– Set whether to use a solar panel application. If you apply solar panel application, you have to change this field
setting value to “1”. The ClimateHub doesn't support a solar panel, as there is no secondary coil in the ClimatHub's
DHW tank.
When the solar application is activated, the compressor (heat pump) and booster heater will not be activated for DHW
mode. The diverter valve switches automatically to space heating position, so that heating is possible during solar
It is possible to operate the heat pump for space heating or cooling simultaneously with the solar panel for DHW
heating.
• #3071 : Water flow direction by 3way diverter valve
– Set default direction of water flow between room and DHW tank.
• #308* : Energy metering
• To check energy information of system, user should set to FSV #308* according to heater (BUH, BSH) capacity.
– In order to get the exact value, this should be set.
0
Please enter your
PASSWORD
Service mode
Service mode
Service Timer
Quiet Mode Automatic Time
Indoor Zone Option
Connection Information
Device Information
Reset All Service Modes
Power Master Reset
ODU K3 Reset
Field Setting Value
Self-Test Mode
Indoor Unit Option
Field Setting Value
10** | Remote Controller
20** | Water Law
30** | DHW
40** | Heat
50** | Others
Simple Setting
FSV Upload/Download
10** | Remote Controller
101* | Water Out Temp. for Cool
102* | Room Temp. for Cool
103* | Water Out Temp. for Heat
104* | Room Temp. for Heat
105* | DHW Tank Temp.
0
Please enter your
PASSWORD
Service mode
Service mode
Service Timer
Quiet Mode Automatic Time
Indoor Zone Option
Connection Information
Device Information
Reset All Service Modes
Power Master Reset
ODU K3 Reset
Field Setting Value
Self-Test Mode
Indoor Unit Option
Field Setting Value
10** | Remote Controller
20** | Water Law
30** | DHW
40** | Heat
50** | Others
Simple Setting
FSV Upload/Download
20** | Water Law
201* | Outdoor Temp. for Water Law
202* | Water Out Temp. for WL1 Heat
203* | Water Out Temp. for WL2 Heat
204* | Heating Water Law for Auto Mode
205* | Outdoor Temp. for Water Law
206* | Water Out Temp. for WL1 Cool
207* | Water Out Temp. for WL2 Cool
0
Please enter your
PASSWORD
Service mode
Please enter your
PASSWORD
Energy Generation
Please enter your
PASSWORD
Energy Consumption
Service mode
Service Timer
Quiet Mode Automatic Time
Indoor Zone Option
Connection Information
Device Information
Reset All Service Modes
Power Master Reset
ODU K3 Reset
Field Setting Value
Self-Test Mode
Indoor Unit Option
Field Setting Value
10** | Remote Controller
20** | Water Law
30** | DHW
40** | Heat
50** | Others
Simple Setting
FSV Upload/Download
30** | DHW
301* | Domestic Hot Water Tank
302* | Heat Pump
303* | Booster Heat
304* | Disinfection
305* | Forced DHW Operation
306* | Solar Panel/DHW Thermostat
307* | Direction of 3Way Valve
308* | Energy Metering
0
Please enter your
PASSWORD
Service mode
Service mode
Service Timer
Quiet Mode Automatic Time
Indoor Zone Option
Connection Information
Device Information
Reset All Service Modes
Power Master Reset
ODU K3 Reset
Field Setting Value
Self-Test Mode
Indoor Unit Option
Field Setting Value
10** | Remote Controller
20** | Water Law
30** | DHW
40** | Heat
50** | Others
Simple Setting
FSV Upload/Download
50** | Others
501* | Outing
502* | DHW Saving
503* | TDM Variable (TDM Product only)
504* | Power Peak Control
505* | Frequency Ratio Control
506* | Heat/DHW Capa. Ratio
508* | PV Control
509* | Smart Grid Control
0
Please enter your
PASSWORD
Service mode
Service mode
Service Timer
Quiet Mode Automatic Time
Indoor Zone Option
Connection Information
Device Information
Reset All Service Modes
Power Master Reset
ODU K3 Reset
Field Setting Value
Self-Test Mode
Indoor Unit Option
Field Setting Value
10** | Remote Controller
20** | Water Law
30** | DHW
40** | Heat
50** | Others
Simple Setting
FSV Upload/Download
40** | Heat
401* | Heat Pump
402* | Backup Heater
403* | Backup Boiler
404* | Mixing Valve
405* | Inverter Pump
406* | Zone Control
(MWR-WW10N)