8. System configuration
Installer reference guide / Mono tank integrated type
131
Space Heating Setting (103* Water out Temp. for heat, 104* Room Temp. for heat)
•
Target water outlet temperature : Upper limit (#1031, Default 70℃, Range : 37 ~ 70℃), Lower limit (#1032, Default
25℃, Range : 15 ~ 37℃)
– With this default FSV settings, the user can change the target water outlet temperature within the range of 15 ~
70℃ for heating.
•
Target room temperature : Upper limit (#1041, Default 30℃), Lower limit(#1042, Default: 16℃)
–
With this default FSV settings, the user can change the target room temperature within the range of 16 ~ 30℃
for heating.
※
Tip: Setting a lower room heating set point may result in saving energy and reducing the energy costs.
DHW Heating Setting (105* DHW Tank Temp.)
•
Target DHW tank temperature. : Upper limit (#1051, Default 55℃, Range : 50 ~ 70℃), Lower limit (#1052, Default 40℃,
Range : 30 ~ 40℃)
–
With this default FSV settings, the user can change the target tank temperature within the range of 30 ~ 70℃
for DHW heating
※
Tip: A lower DHW set temperature may result in a higher efficiency of the heat pump, but it may limit the total number
of showers before recharging.