8. System configuration
Installer reference guide / Mono tank integrated type
140
4) Periodical Disinfection heating of water tank (#304*)
Main Menu
(FSV)
Sub Menu Function
Description
FSV Step
Unit
Default
Min.
Max.
DHW
FSV 30**
Disinfection
Application
3041
-
-
1 (On)
0 (Off)
1
Interval
3042
1
day
Fri (5) Sun (0) All (7)
Start Time
3043
1
o'clock
23
0
23
Target Temp.
3044
5
˚C
70
40
70
Duration
3045
5
min
10
5
60
Max time
3046
1
hour
8
1
24
#3043 : Start time for disinfection (0~24hr)
#3044 : Target temp.for disinfection
#3045 : Time duration which satisfy the target temp. for
disinfection
#3044
#3045
#3042
#3043
5) Forced DHW operation (#305*)
Main Menu
(FSV)
Sub Menu Function
Description
FSV Step
Unit
Default
Min.
Max.
DHW
FSV 30**
Forced DHW
Operation
Timer OFF Function
3051
-
-
0 (No)
0
1 (Yes)
Time Duration
3052
1
(x10)min
6
3
30
• Forced DHW mode shall be working depending on timer setting.
• #3051 : Set whether to use a timer for forced DHW function
.
• #3052 : Set time for forced DHW operation
.