© 20
20
Samsung All rights reserved.
Step
Button press
Display
Description
Note
Step 1
Power on unit
id nd
Indoor setting
required
-
Quantity of indoor units
Step 2
Press K1 & K2 for 2
seconds
id 00
Ready to set
(Default)
Step 3
K2
id
X
0
Ten digit setting
-
K4
id 0
X
Ones digit setting
Hold K4 for 2 seconds to start auto detection mode
Heat pumps hold K2 to save and exit. Segment will display Ad 00 then UP.
Quantity of MCU (HR only)
Step 4
Press K1
NC 00
Ready to set
(Default)
Step 5
K2
NC
X
0
Ten digit setting
-
K4
NC 0
X
Ones digit setting
Hold K4 for 2 seconds for auto detection mode
Heat recovery setting
Step 6
Press K1
ht 00
System type
-
Step 7
Press K4
ht 00
Heat pump
(Default)
ht 01
Heat Recovery
Must set
Step 8
Hold K2
Exit
Save
Unit will display
E201 or E213
All units powered on
Indoor unit count
Outdoor Type
Finished
MCU count
HR only
60 Btu HP/HR Initial system settings