41
SET
TING
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Description
Page
FCU KIT pipe installation
structure
-
Valve open control when
Thermo Off
-
FCU cool air prevention
compensation temperature
Display/
detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
2
0
2-pipe
-
0
Valve close
(normally close
type)
-
0
0 °C (0 °F)
1
4-pipe
1
Valve open
(normally close
type)
1
1 °C (1,8 °F)
2
2 °C (3,6 °F)
3
3 °C (5,4 °F)
4
4 °C (7,2 °F)
5
5 °C (9,0 °F)
6
6 °C (10,8 °F)
7
7 °C (12,6 °F)
8
-7 °C (-12,6 °F)
9
-6 °C (-10,8 °F)
A
-5 °C (-9,0 °F)
B
-4 °C (-7,2 °F)
C
-3 °C (-5,4 °F)
D
-2 °C (-3,6 °F)
E
-1 °C (-1,8 °F)
F
0 °C (0 °F)
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Description
Page
-
-
-
Setting cool/warm air
prevention skip
FCU KIT external room sensor
Display/
detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
3
-
-
-
0
Use in cool
Use in heat
0
Disuse
1
Disuse in cool
Use in heat
1
Enable
2
Use in cool
Disuse in heat
3
Disuse in cool
Disuse in heat
y
Valve open control when Thermo Off: Set to open valve when Thermo Off in case of
applying Close type water valve (Valve closes normally if it is not set.)
y
FCU cool air prevention compensation temperature: Temperature for preventing cool air
can be controlled.
– Default temp. + SEG18 ≥Water-IN temp. (°C): Heating fan On
– Default temp. + SEG18 < Water-IN temp. (°C): Heating fan Off
y
Fan speed can be various according to the water in temperature.
Содержание DVM
Страница 48: ......