Essential
2. Specification
22
Type
DVM S
DVM S
Model Name
AM380MXVDGH/ET
AM400MXVDGH/ET
Outdoor unit module 1
AM120MXVDGH/ET
AM120MXVDGH/ET
Outdoor unit module 2
AM120MXVDGH/ET
AM140MXVDGH/ET
Outdoor unit module 3
AM140MXVDGH/ET
AM140MXVDGH/ET
Outdoor unit module 4
-
-
Wiring
connections
Transmission Cable
mm
2
0.75
0.75
Remark
-
F1, F2
F1, F2
Power supply intake
-
Both indoor and outdoor unit
Both indoor and outdoor unit
Refrigerant
Type
-
R410A
R410A
Factory Charging
kg
6.5 x 2 + 7.7 x 1
6.5 x 1 + 7.7 x 2
tCO
2
e
43.22
45.73
Sound
Sound Pressure
Cooling
dB(A)
66
66
Heating
dB(A)
68
68
Sound Power
dB(A)
86
86
External
Dimension
Net Weight
kg
210.0 x 2 + 226.0 x 1
210.0 x 1 + 226.0 x 2
Shipping Weight
kg
217.0 x 2 + 246.0 x 1
217.0 x 1 + 246.0 x 2
Net Dimensions (WxHxD)
mm
(880 x 1,695 x 765) x 2 +
(1,295 x 1,695 x 765) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 2
Shipping Dimensions (WxHxD)
mm
(948 x 1,887 x 832) x 2 +
(1,363 x 1,887 x 832) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 2
Operating
Temp. Range
Cooling
℃
-5 ~ 48
-5 ~ 48
Heating
℃
-25 ~ 24
-25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
※
Eurovent certified
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
5) Sound values of multi combination are theoretical values based on sound results of individual installed units.
6) These products contain R410A (GWP=2,088) which is fluorinated greenhouse gas.
7) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.