Refrigerant pipe installation
Refrigerant pipe installation
f
Basic amount of refrigerant within the outdoor unit (kg)
-Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Classification AM080JXVHGH/EU AM100JXVHGH/EU AM120JXVHGH/EU AM140JXVHGH/ET AM160JXVHGH/ET AM180JXVHGH/ET
Basic amount
6.5
6.5
6.5
9.4
9.4
8.4
Classification AM200JXVHGH/ET AM220JXVHGH/ET AM240KXVGGH/ET AM260KXVGGH/ET AM280KXVGGH/ET
Basic amount
11.0
11.0
14.0
14.0
14.0
Classification AM080JXVAGH/EU AM100JXVAGH/EU AM120JXVAGH/EU AM140KXVAGH/ET AM160KXVAGH/ET AM180KXVAGH/ET
Basic amount
5.5
5.5
6.5
7.7
8.4
8.4
Classification AM200KXVAGH/ET AM220KXVAGH/ET AM240KXVAGH/ET AM260KXVAGH/ET AM280KXVAGH/ET AM300KXVAGH/ET
Basic amount
8.4
8.4
14.0
14.0
14.0
14.0
Classification AM100MXVDGH/ET AM120MXVDGH/ET AM140MXVDGH/ET AM160MXVDGH/ET AM180MXVDGH/ET
Basic amount
5.5
6.5
7.7
8.4
8.4
Classification AM080JXVHGR/EU AM100JXVHGR/EU AM120JXVHGR/EU AM140JXVHGR/ET
AM160JXVHGR/ET
AM180JXVHGR/ET
Basic amount
6.5
6.5
6.5
9.4
9.4
8.4
Classification AM200JXVHGR/ET AM220JXVHGR/ET AM240MXVGNR/ET AM260MXVGNR/ET AM280MXVGNR/ET AM300MXVANR/ET
Basic amount
11.0
11.0
14.0
14.0
14.0
14.0
f
Amount of additional refrigerant depending on the pipe size (
ⓐ
)
-Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe
Ø 6.35
Ø 9.52
Ø 12.70 Ø 15.88 Ø 19.05 Ø 22.22 Ø 25.40 Ø 28.58
Additional amount (kg/m)
0.02
0.06
0.125
0.18
0.27
0.35
0.53
0.65
-For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter regardless
of the pipe size.