Space Requirements for Outdoor Unit
When installing 1 outdoor unit
300 or mor
e
When the air outlet is opposite
the wall
1500 or mor
e
When the air outlet is towards the
wall
300 or mor
e
150 or more
600 or more
When 3 sides of the outdoor unit
are blocked by the wall
1500 or mor
e
2000 or more
The upper part of the outdoor unit
and the air outlet is towards the wall
500 or mor
e
300 or more
The upper part of the outdoor
unit and the air outlet is opposite
the wall
When the walls are blocking front
and the rear side of the outdoor
unit
300 or mor
e
1500 or mor
e
Top view
Side view
Air outlet
Air intake
Air intake
Air outlet
Figure Description
,
Air flow direction
.
(Unit : mm)
When installing more than 1 outdoor unit
(Unit : mm)
1500 or mor
e
When the air outlet is towards the wall
When 3 sides of the outdoor unit are blocked by the wall
300 or mor
e
300 or more
600 or more
600 or more
600 or more
Choosing the installation location
English-31
In
St
A
ll
At
IO
n
05
NA_GOOD_A3050_IB&IM_EN_DB68-04387A-00.indd 31
11/26/2013 9:56:00 PM