Changing a particular option
❇
❇
Particular option can be set with a wireless remote controller only .
You can change each digit of set option .
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Description
Page
Mode
Option mode to
change
Tens digit of option
SEG to change
Unit digit of option
SEG to change
Changed value
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0
D
Option
mode
0~F Tens digit of
SEG
0~9 Unit digit of
SEG
0~9
Changed
value
0~9
f
f
If you want to change the one digit of the installation option 1 of the ERV, set the SEG3 to "2" .
f
f
If you want to change the one digit of the installation option 2 of the ERV, set the SEG3 to "5" .
Example) To set "Virus doctor control" to "use" among installation option
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Description
Page
Mode
The option mode you
want to change
Tens digit of option
SEG to change
Unit digit of option
SEG to change
Changed value
Settings
0
D
2
1
6
1
Example) To set "CO
2
sensor" to "use" among installation option
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Description
Page
Mode
The option mode you
want to change
Tens digit of option
SEG to change
Unit digit of option
SEG to change
Changed value
Settings
0
D
5
1
5
1
Example) To set "Centralized control" to "use" among installation option (Default: Enable)
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Description
Page
Mode
The option mode you
want to change
Tens digit of option
SEG to change
Unit digit of option
SEG to change
Changed value
Settings
0
D
2
0
5
0
Example) To set "Filter usage hours" to "2000 Hour" among installation option
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Description
Page
Mode
The option mode you
want to change
Tens digit of option
SEG to change
Unit digit of option
SEG to change
Changed value
Settings
0
D
2
1
8
6
Example) To set "Humidification" to "use" among installation option
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Description
Page
Mode
The option mode you
want to change
Tens digit of option
SEG to change
Unit digit of option
SEG to change
Changed value
Settings
0
D
5
1
4
1
Example) To set "External damper" to "use" among installation option
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Description
Page
Mode
The option mode you
want to change
Tens digit of option
SEG to change
Unit digit of option
SEG to change
Changed value
Settings
0
D
5
1
6
1
Example) To set "Reverse installation" among installation option
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Description
Page
Mode
The option mode you
want to change
Tens digit of option
SEG to change
Unit digit of option
SEG to change
Changed value
Settings
0
D
5
1
7
1