![Samsung AN026JSKLKN Series Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/samsung/an026jsklkn-series/an026jsklkn-series_installation-manual_344355035.webp)
Setting the address of ERV (MAIN/RMC)
1 . Check whether power is supplied to the ERV or not .
- When the power is not supplied to the ERV, there should be additional power supply to it .
2 . Depending on the installation condition of the ERV, each ERV's address (MaIn/RMC) should be set .
3 . Set the ERV's address (MaIn/RMC) by using a remote controller .
- Initial address of the ERV is set as follows; "MaIn:0, RMC:0"
- Set MaIn and RMC address only when it is necessary . When ERV interface module assigns address automatically,
setting the MaIn address is unnecessary and even though the MaIn address is set, the ERV will follow the address
assigned by the ERV interface module .
- Default value will be maintained when you input the numbers that shouldn't be set on each SEG . (If you input any
number in SEG13~24, the value will be ignored .)
- If you input any value on the SEG with "no function", it will be ignored .
4 . Use a wired/wireless remote controller to set the option . When setting the option with wireless remote controller,
receiving module for remote controller is embedded in PBa so there's no need for connecting extra panel .
option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Description
Page
Mode
Setting main address
no function
10-digit of ERV
The unit digit of an
ERV
Indication
and Details
Indication Details Indication Details Indication
Details
Indication Details Indication Details
0
a
0
no main address
0~4
10-digit
0~9
Unit digit
1
address setting
mode
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Description
Page
no function
Setting RMC address
no function
Group channel
Group address
Indication
and Details
Indication Details
Indication
Details
Indication Details Indication Details
1
0
no main address
RMC1
0~2
RMC2
0~F
1
address setting
mode
Example) To set "MaIn address: 3/ Group channel: 1/ RMC address: B", you may set the option as shown in the following table
(excluding SEG1 and SEG7 which is page option) .
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
a
1
-
-
3
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
-
1
-
1
B
•
Main address can be set from 0~47 only and if any other values are set, 'communication error' will occur .
•
If you set the SEG3 as 0, the ERV will maintain the existing main address even if you input the option value of
SEG6 .
•
If you set the SEG9 as 0, the ERV will maintain existing RMC address even if you input the option value of
SEG11~12 .
CAUtIoN
ENGLISH-35
03
o
tHERS
ERV_IM_EN_DB68-05252A-02.indd 35