34
Installation Procedure
Instal
lation Pr
oc
edur
e
English
(*1)
Height difference : The difference of the height between the corresponding indoor unit and the indoor unit
installed at the lowest place. For example, When the indoor unit is installed 131.23ft. (40m) higher than the indoor
unit installed at the lowest place, select the option “1”.
(*2)
The difference between the pipe length of the indoor unit installed at farthest place from an outdoor unit and the
pipe length of the corresponding indoor unit from an outdoor unit.
For example, when the farthest pipe length is 328 ft. (100 m) and the corresponding indoor unit is 131.23 ft. (40 m)
away from an outdoor unit, select the option “2”. (100 - 40 = 196.85 ft. (60m))
(*3)
For MTFC option, MTFC(Multi Tenant Function Controller) kit is required.
(*4)
Heater operation when the SEG9 of 02 series installation option is set to using hot water heater or when SEG15 is
set to using external heater.
Example 1) Setting 02 series SEG9 =”1” / Setting 05 series SEG18 = “0”: The hot water heater is turned on at the
same time as the heating thermostat is on, and turned off when the heating thermostat is off.
Example 2) Setting 02 series SEG15 =”2” / Setting 05 series SEG18 =”A”: Room temp. ≤ set temp. + f (heating
compensation temp.)
– External heater is turned on when the temperature is maintained as 40.1 °F (4.5 °C) for 10 minutes. Room temp. >
set temp. + f(heating compensation temp.)
– External heater is turned off when the temperature is maintained as 40.1 °F (4.5 °C) + 33.8 °F (1 °C) (33.8 °F (1 °C)
is the Hysteresis for On/Off selection.)
Additional information on SEG 3, 4, 5, 6, 8, 9
When SEG 3 is set to 1 and the HR-specific auto changeover function is run, the indoor unit operates as shown in the
following figure:
C
Temperature
b
d
c
A
D
B
a
Ts
Set temperature
for Auto mode
Reference
temperature for
cooling
Reference temperature for heating
Reference temperature for change from
heating to cooling
Reference temperature for
cooling
Cool
ing th
ermo
off
Cool
ing th
ermo
on
Heating th
ermo
off
Heating th
ermo
on
A: Set with SEG4 (˚C)
B: Set with SEG5 (˚C)
C: Set with SEG6 (˚C)
D: Set with SEG8 (˚C)
The mode change between the Cool and Heat modes is made only when the thermo off state is maintained for the
period of time set with SEG9.
Cool
ing Th
ermo Off
He
ating Th
ermo Off
He
ating Th
ermo On
Cool
ing Th
ermo On
Temperature
Reference temperature for change from heating
to cooling
Reference temperature for cooling
Reference temperature for heating
A : Set with SEG4°F(°C)
B : Set with SEG5°F(°C)
C : Set with SEG6°F(°C)
D : Set with SEG8°F(°C)
Reference temperature for
cooling
Set temperature for Auto
mode