33
Instal
lation Pr
oc
edur
e
English
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Explanation
-
-
-
-
-
Control variables when using hot water / external heater (*4)
Indication
and Details
Indication Details
-
-
-
-
Indication
Details
Set temp for heater On/Off Delay time for heater On
2
-
-
-
-
0
At the same time as thermo on
No delay
1
At the same time as thermo on
10 minutes
2
At the same time as thermo on
20 minutes
3
34.7 °F (1.5°C)
No delay
4
34.7 °F (1.5°C)
10 minutes
5
34.7 °F (1.5°C)
20 minutes
6
37.4 °F (3°C)
No delay
7
37.4 °F (3°C)
10 minutes
8
37.4 °F (3°C)
20 minutes
9
40.1 °F (4.5°C)
No delay
A
40.1 °F (4.5°C)
10 minutes
B
40.1 °F (4.5°C)
20 minutes
C
42.8 °F (6.0°C)
No delay
D
42.8 °F (6.0°C)
10 minutes
E
42.8 °F (6.0°C)
20 minutes
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
-
-
-
Forcing FAN Operation for Heating and Cooling
-
Indication
and Details
Indication Details
-
-
-
Indication
Details
-
Cooling Fan
Setting
Heating Fan
Setting
3
-
-
-
0
Disuse
Disuse
-
1
Disuse
Use (Fan: User
setting)
2
Disuse
Use (Fan: High)
3
Disuse
Use (Fan: Low)
4
Use (Fan: User
setting)
Disuse
5
Use (Fan: User
setting)
Use (Fan: User
setting)
6
Use (Fan: User
setting)
Use (Fan: High)
7
Use (Fan: User
setting)
Use (Fan: Low)
8
Use (Fan: High)
Disuse
9
Use (Fan: High)
Use (Fan: User
setting)
A
Use (Fan: High) Use (Fan: High)
B
Use (Fan: High) Use (Fan: Low)
C
Use (Fan: Low)
Disuse
D
Use (Fan: Low)
Use (Fan: User
setting)
E
Use (Fan: Low) Use (Fan: High)
F
Use (Fan: Low)
Use (Fan: Low)