Step 8 Performing the gas leak test
To identify potential gas leaks on the indoor unit, inspect
the connection area of each refrigerant pipe using a leak
detector for R-410A.
Before recreating the vacuum and recirculating the
refrigerant gas, pressurize the whole system with nitrogen
(using a cylinder with a pressure reducer) at a pressure
above 0.2 MPa, less than 4 MPa (gauge) in order to
immediately detect leaks on the refrigerant fittings.
Made vacuum for 15 minutes and pressurizing system with
nitrogen.
Liquid side
Gas side
Insulator
Step 9 Insulating the refrigerant pipes
Once you have checked that there are no leaks in the
system, you can insulate the piping and hose.
1
To avoid condensation problems, place Acrylonitrile
Butadien Rubber separately around each refrigerant
pipe.
No gap
NBR
NOTE
•
Always make the seam of pipes face upwards.
CAUTION
•
The insulation has to be produced in full compliance
with European regulation EEC / EU 2037 / 2000
requring the use of sheaths insulation without using
CFC and HCFC gases for heating and the environment.
2
Wind insulating tape around the pipes and drain hose
avoiding compressing the insulation too much.
Insulation cover pipe
Insulation pipe
Be sure to overlap the insulation.
Indoor unit
CAUTION
•
Be sure to wrap insulation tightly without any gaps.
3
Finish wrapping insulating tape around the rest of the
pipes leading to the outdoor unit.
4
The pipes and electrical cables connecting the indoor
unit with the outdoor unit must be fixed to the wall
with suitable ducts.
CAUTION
•
Must fit tightly against body without any gap.
•
Make sure that all refrigerant connection must be
accessible for easy maintenance and detachment.
•
Install the insulation not to get wider and use the
adhesives on the connection part of it to prevent
moisture from entering.
•
Wind the refrigerant pipe with insulation tape if it is
exposed to outside sunlight.
•
Install the refrigerant pipe respecting that the insulation
does not get thinner on the bent part or hanger of pipe.
•
Add the additional insulation if the insulation plate
gets thinner.
a x 3
Hanger
Additional insulation
a
Refrigerant pipe
insulation
Liquid side
Gas side
Insulator
No gap
Indoor unit
Insulation cover pipe
Insulation pipe
Be sure to overlap the insulation.
Additional insulation
Hanger
Refrigerant pipe
insulation