31
ENGLISH
05 series installation option(Detailed)
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Use of Auto Change
Over for HR only in
Auto mode
(When setting SEG3)
Standard heating temp.
Offset
(When setting SEG3)
Standard cooling
temp. Offset
(When setting SEG3)
Standard for mode
change
Heating
Cooling
Remote
Controller
Display
Indication and
Details
Indication Details Indication Details Indication Details Indication
Details
Indication Details Indication Details
0
5
0
Follow
product
option
0
0
0
0
0
1
1
Use Auto
Change
Over for
HR only
1
0.5
1
0.5
1
1.5
2
1
2
1
2
2
3
1.5
3
1.5
3
2.5
4
2
4
2
4
3
5
2.5
5
2.5
5
3.5
6
3
6
3
6
4
7
3.5
7
3.5
7
4.5
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
(When setting SEG3)
Standard for mode
change
Cooling
Heating
(When setting SEG3)
Time required for
mode change
Compensation option
for Long pipe or height
diffference between indoor
units
Remote
Controller
Display
Indication and
Details
Indication Details Indication Details Indication Details Indication
Details
1
0
1
0
5 min.
0
Use default value
1
1.5
1
7 min.
1
1) Height
difference
1)
is
more than 30m
or
2) Distance
2)
is
longer than 110m
2
2
2
9 min.
3
2.5
3
11 min.
4
3
4
13 min.
2
1) Height
difference
1)
is
15~30m
or
2) Distance
2)
is
50~110m
5
3.5
5
15 min.
6
4
6
20 min.
7
4.5
7
30 min.