background image

17

ENGLISH

5. 

Select the insulation of the refrigerant pipe.

•  Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size.
•  Indoor temperature of 30°C and humidity of 85% is the standard condition. 

If install in a high humidity condition,use one grade thicker insulator by referring to the table below. 
If installing in an unfavorable conditions, use thicker one.

•  Insulator’s heat-resistance temperature should be more than 120°C.

Pipe size (mm)

Minimum thickness of insulator (mm)

Remarks

PE foam

EPDM foam

Ø6.35~Ø15.88

13

10

If you install the pipe underground, at the 

seaside, a spa or on the lake, use 1 grade thicker 

one according to the pipe size.

-

25

19

Refrigerant pipe before EEV kit and MCU or without EEV kit and MCU

•  You can contact the gas side and liquid side pipes but the pipes should 

not be pressed.

•  When contacting the gas side and gas side pipe, use 1 grade thicker 

insulator.

Gas pipe

Liquid pipe

Insulation

Insulation

Refrigerant pipe after EEV kit and MCU

•  Install the gas side and liquid side pipes, leave 10mm of space.
•  When contacting the gas side and liquid side pipe, use 1 grade thicker 

insulator.

Gas pipe

10mm

10mm

10mm

Liquid pipe

•  Install the insulation not to get wider and use the adhesives on the connection part of it to prevent 

moisture from entering.

•  Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight.
•  Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or 

hanger of pipe.

•  Add the additional insulation if the insulation plate gets thinner.

Additional insulation

Hanger

Refrigerant pipe insulation

a×3

a

CAUTION

Содержание AM FNCD Series

Страница 1: ...Convertible Type Series Ceiling Floor AM FNCD Air Conditioner installation manual imagine the possibilities Thank you for purchasing this Samsung product DB68 03880A 05 EN TR RU UK KK IN FR AR...

Страница 2: ...connection of electric and hydraulic lines Failure to comply with these instructions or to comply with the requirements set forth in the Operating limits table included in the manual shall immediately...

Страница 3: ...applications for which it has been designed the indoor unit is not suitable to be installed in areas used for laundry X X Our units must be installed in compliance with the spaces indicated in the ins...

Страница 4: ...itioner in following places Place where there is mineral oil or arsenic acid Resin parts flame and the accessories may drop or water may leak The capacity of the heat exchanger may reduce or the air c...

Страница 5: ...s present in the air Avoid location where obstacles preventing good air circulation are present Noise prevention should be considered in determining the unit s location The structure where the unit is...

Страница 6: ...t b o tto m sid e A ir in ta k e h o le 5 0 W irin g h o le D ra in h o se o u tle t 2 1 3 Pipe outlet bottom side Drain hose outlet Wiring hole Air intake hole 50 50 44 No Name Description 1 Liquid p...

Страница 7: ...40 650 Unit mm 3 IInstall the unit onto the ceiling Be sure to arrange the drain hose so that it is leveled lower than the drain hose connecting port of the indoor unit NOTE For proper drainage of con...

Страница 8: ...downwards toward the outdoor for smooth water flow NOTE Use the pattern sheet to select pipe directions 300mm or more 300mm or more 2 Install the hanging plate according to the distance and mount it 3...

Страница 9: ...eld supply Hole in anchor Hole in plug Insert Unit mm 450mm X 200mm or more Maintenance Hole Maintenance hole must be located on the ceiling Indoor unit pipe connection Outdoor uint pipe connection Dr...

Страница 10: ...nit test the strength of each attached suspension bolt CAUTION 2 Connect the IN refrigerant pipe to the outdoor unit 3 Connect the OUT refrigerant pipe to each indoor unit A B and C The liquid and gas...

Страница 11: ...in pipe A the EEV kit A address should be set as 03 A Function of Display The numbers which are displayed on left are the status of indoor unit checking status through communication with same outdoor...

Страница 12: ...the same time pipe cross connection and address mismatching cannot be found CAUTION Purging the unit On delivery the indoor unit is loaded with an inert Nitrogen gas All this gas must therefore be pur...

Страница 13: ...2 Remove the pinch pipe on the pipes and connect the assembly pipes to each pipe tightening the nuts first manually and then with a torque wrench a spanner applying the following torque Outer Diameter...

Страница 14: ...rectly cut edges below 90 Oblique Rough Burr 3 To prevent a gas leak remove all burrs at the cut edge of the pipe using a reamer 4 Carry out flaring work using flaring tool as shown below Flaring tool...

Страница 15: ...ten the flare nuts first manually and then with a torque wrench applying the following torque Outer diameter mm Connection Torque Flare dimension mm Flare shape mm kgf cm N m 6 35 140 180 14 18 8 70 9...

Страница 16: ...lation Once you have checked that there are no leaks in the system you can insulate the piping and hose 1 To avoid condensation problems place T13 0 or thicker Acrylonitrile Butadien Rubber separately...

Страница 17: ...or without EEV kit and MCU You can contact the gas side and liquid side pipes but the pipes should not be pressed When contacting the gas side and gas side pipe use 1 grade thicker insulator Gas pipe...

Страница 18: ...check that none of the following situations occur 5cm less Ditch The hose must not slope upwards The end of the drain hose must not be placed in water Do not bend the hose in different directions Kee...

Страница 19: ...the wired remote control N L N L N L N L ELCB MCCB ELB V1 V2 Indoor Unit 1 Indoor Unit 2 Indoor Unit 3 Indoor Unit 4 Indoor Unit 5 Indoor Unit 6 Outdoor Unit Wired Remote Control EEV kit Ceiling wall...

Страница 20: ...57 CENELEC H05RN F or IEC 60245 IEC 66 CENELEC H07RN F The capacity of ELCB or MCCB ELB X A 1 25 X 1 1 X Ai X The capacity of ELCB or MCCB ELB Ai Sum of Rating currents of each indoor unit Refer to ea...

Страница 21: ...or MCCB ELB Apply following equation n k 1 Coef 35 6 Lk ik 10 of input voltage V 1000 Ak Calculation Installing with 1 sort wire 220 V 2 2 V 2 0 V 2 5 mm2 208 8 V Within 198V 242V 2 2 2 0 1 8 1 5 1 3...

Страница 22: ...ole disconnection from the power supply must be incorporated in the fixed wiring 3mm You must keep the cable in a protection tube Keep distances of 50mm or more between power cable and communication c...

Страница 23: ...air conditioner on or off Temperature Adjusts the temperature Options Selects options during operation Direction Moves to select and set an option Timer Sets timer option Step 1 Entering mode to set o...

Страница 24: ...to enter SEG8 value Each time you press the button will be selected in rotation SEG6 SEG8 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Pr...

Страница 25: ...to enter SEG21 value Press High Fan button to enter SEG22 value Each time you press the button will be selected in rotation SEG21 SEG22 18 Setting Heat mode Press Mode button to be change to HEAT mod...

Страница 26: ...it The unit digit of an indoor unit Remote Controller Display Indication and Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0...

Страница 27: ...ion SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 1 Drain pump Hot water heater EEV Step when heating stops SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 2 External control External control output External heater On or Off...

Страница 28: ...erationwhen thermostatisoff Useofcentralcontrol FANRPMcompensation Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details Indicatio...

Страница 29: ...troller Heatingsettingcompensation Removingcondensatedwaterin heatingmode EEVStepofstoppedunit duringoilreturn defrost mode Motiondetectsensor Remote Controller Display Indication andDetails Indicatio...

Страница 30: ...4Way Cassette 5 C Other indoor units 2 C 5 This function can be applied to 4Way Cassette and Mini 4Way Cassette only If the air conditioner operates the heating mode immediately after finishing the co...

Страница 31: ...Change Over for HR only 1 0 5 1 0 5 1 1 5 2 1 2 1 2 2 3 1 5 3 1 5 3 2 5 4 2 4 2 4 3 5 2 5 5 2 5 5 3 5 6 3 6 3 6 4 7 3 5 7 3 5 7 4 5 Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE When settin...

Страница 32: ...nstalled at the lowest place select the option 1 2 Distance The difference between the pipe length of the indoor unit istalled at farthest place from an outdoor unit and the pipe length of the corresp...

Страница 33: ...SEG5 C C Set with SEG6 C D Set with SEG8 C Cooling Thermo Off Heating Thermo Off Cooling Thermo On Heating Thermo On B C D Ts A c a Temp d b Standard temp for Heating Standard temp for Cooling Standar...

Страница 34: ...hen changing a digit of an indoor unit address setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disus...

Страница 35: ...w the steps below Providing information for user After finishing the installation of the air conditioner you should explain the following to the user Refer to appropriate pages in the User s Manual 1...

Страница 36: ...Open E221 X X X 2 Error on cond sensor E237 3 Error on discharge sensor E251 Other outdoor unit sensor error that is not on the above list 1 When there is no communication between the indoor outdoor...

Страница 37: ...l E413 13 Compressor down due to low pressure sensor prevention control_1 E410 14 Simultaneous opening of cooling heating MCU SOL valve 1st detection E180 15 Simultaneous opening of cooling heating MC...

Страница 38: ...door units refer to the installation manual CAUTION Unit mm 120 60 20 20 20 180 Power cable provided by us 20 Wire tube power cable 3 Insert both sides of core wire of the power cable into the connect...

Страница 39: ...be contraction work is completed wrap it with the insulation tape to finish Make sure that the connection parts are not exposed to outside Be sure to use insulation tape and a contraction tube made of...

Страница 40: ......

Отзывы: