Connecting the refrigerant pipe
There are two refrigerant pipes of differing diameters:
• A smaller one for the liquid refrigerant
• A larger one for the gas refrigerant
• The inside of copper pipe must be clean & has no dust.
1.
Before connecting the refrigerant pipe, open the cover side.
2.
Remove the pinch pipe on the pipes and connect the assembly pipes
to each pipe, tightening the nuts, first manually and then with a torque
wrench, a spanner applying the following torque.
Outer Diameter (mm)
Torque
kgf•cm
N•m
6.35
140~180
14~18
9.52
350~430
34~42
12.70
500~620
49~61
15.88
690~830
68~82
NOTE
• Must apply refrigerant oil on the flaring area to prevent a
leak.
Refrigerant oil
Torque wrench
Flare nut
Union
Spanner
3.
Be sure that there must be no crack or kink on the bended area.