![background image](http://html1.mh-extra.com/html/samsung/aj-cxs-ch-series/aj-cxs-ch-series_installation-manual_4746866016.webp)
16
Installation Procedure
English
Instal
lation Pr
oc
edur
e
◆ AJ024CXS4CH
1
Piping outside diameter.
Indoor unit
Out unit
Power
supply Ø,
V, Hz
Outside
diameter
Liquid Gas
**07/09/12/009/
012**, AR15**
AJ024CXS4CH
1,208-
230,60
1/4"
3/8"
**18/018**
AJ015**, AC015**
1/2"
A
B
(h) (H)
C
D
Main power switch
2
Piping length and the height.
1 Room
max
length
4 Room
total max
length
Max height
between
indoor unit &
outdoor unit
Max height
between
indoor
units
Dimension
82.0 ft
(25 m)
229.7 ft
(70 m)
49.2 ft
(15 m)
24.6 ft
(7.5 m)
Composition A,B,C,D A+B+C+D
(H)
(h)
Make at least one round:
It will reduce noise and vibration
CAUTION
• Minimum pipe length is 10 ft (3 m) to reduce noise and
vibration.
• The appearance of the unit may be different from the
diagram depending on the model.
◆ AJ030CXS4CH / AJ036CXS4CH / AJ036BXJ4CH
1
Piping outside diameter.
Indoor unit
Out unit
Power
supply Ø,
V, Hz
Outside
diameter
Liquid Gas
**07/09/12/009/
012**, AR15** AJ030CXS4CH /
AJ036CXS4CH /
AJ036BXJ4CH
1,208-
230,60
1/4"
3/8"
**18/018**
AJ015**, AC015**
1/2"
**24/024**
5/8"
A
B
(h) (H)
C
D
Main power switch
2
Piping length and the height.
1 Room
max
length
4 Room
total max
length
Max height
between
indoor unit &
outdoor unit
Max height
between
indoor
units
Dimension
82.0 ft
(25 m)
229.7 ft
(70 m)
49.2 ft
(15 m)
24.6 ft
(7.5 m)
Composition A,B,C,D A+B+C+D
(H)
(h)
Make at least one round:
It will reduce noise and vibration
CAUTION
• Minimum pipe length is 10 ft (3 m) to reduce noise and
vibration.
• The appearance of the unit may be different from the
diagram depending on the model.
DB68-12535A-00_IM_23Y FJM Outdoor_AA_EN_.indd 16
DB68-12535A-00_IM_23Y FJM Outdoor_AA_EN_.indd 16
2023-09-22 오후 1:46:56
2023-09-22 오후 1:46:56