7
English
Instal
lation Pr
oc
edur
e
When installing more than 1 outdoor unit
Unit: inch (mm)
59.06 (1500)
or more
23.62 (600)
or more
118.11 (3000)
or more
118.11 (3000)
or more
11.81 (300)
or more
23.62 (600)
or more
23.62 (600)
or more
59
.06 (
1500)
or mor
e
11.
81 (
300)
or mor
e
23.62 (600)
or more
23.62 (600)
or more
59
.06 (
1500)
or
mor
e
23.62 (600)
or more
23.62 (600)
or more
23.62 (600)
or more
11.81
(300) or more
11
.81 (
300)
or
mor
e
11.81 (300) or more
11.81 (300) or more
19
.69 (
500) or
mor
e
19
.69 (
500) or
mor
e
CAUTION
• The outdoor unit must be installed according to the specified
distances in order to permit accessibility from each side, to
guarantee correct operation, maintenance, and repair of the
unit.
The components of the outdoor unit must be reachable and
removable under safe conditions for people and the unit.
Step 2 Checking and preparing
accessories and tools
3-wire
Power Cable (option)
2-wire
Assembly Cable (option)
Drain Plug
Energy Label
Federal law prohibits removal of this label before consumer purchase.
U.S. Government
Heat Pump
Cooling and Heating
Split System
Samsung Electronics Co., Ltd.
Model AJ036JCJ5CH
Heating Capacity 40,000 Btu/h
Cooling Capacity 36,000 Btu/h
13.5
Most Efficient
Range of Similar Models
* Heating Seasonal Performance Factor
Least Efficient
8.2
9.0-9.5
Heating
Efficiency Rating (HSPF)*
30.5
Most Efficient
Range of Similar Models
* Seasonal Energy Efficiency Ratio
Least Efficient
14.0
16.5-18.5
Cooling
Efficiency Rating (SEER)*
For energy cost info, visit
productinfo.energy.gov
This system’s
efficiency ratings depend
on the coil your contractor
installs with this unit. The
heating efficiency rating
varies slightly in different
geographic regions. Ask
your contractor for details.
Rubber Leg
Installation Manual
Flare Nuts, 5/8 inch (15.88 mm)
outer pipe diameter
(AJ030CXS4CH, AJ036CXS4CH,
AJ036BXJ4CH, AJ048BXJ5CH)
Flare Nuts, 3/8 inch (9.52 mm)
outer pipe diameter
(AJ024CSX4CH, AJ030CXS4CH,
AJ036CXS4CH, AJ036BXJ4CH,
AJ048BXJ5CH)
Tube connector
[Pipe 1/2 inch (12.7 mm);
Bolt 3/8 inch (9.52 mm)]
(AJ024CSX4CH, AJ030CXS4CH,
AJ036CXS4CH, AJ036BXJ4CH,
AJ048BXJ5CH)
Tube connector
[Pipe 1/2 inch (12.7 mm);
Bolt 5/8 inch (15.88 mm)]
(AJ030CXS4CH, AJ036CXS4CH,
AJ036BXJ4CH, AJ048BXJ5CH)
Drain Cap
NOTE
• Wire assembly cables are optional. If they are not
supplied, use standard cables.
• The drain plug and the rubber legs are included only when
the air conditioner is supplied without assembly pipes.
• If these accessories are supplied, they are in the
accessory package or outdoor unit package.
DB68-12535A-00_IM_23Y FJM Outdoor_AA_EN_.indd 7
DB68-12535A-00_IM_23Y FJM Outdoor_AA_EN_.indd 7
2023-09-22 오후 1:46:54
2023-09-22 오후 1:46:54