24
Installation Procedure
English
Instal
lation Pr
oc
edur
e
Example)
• If you have selected desired option, you can shortly press the K2 switch to adjust the value of the Seg 3, Seg 4 and
change the function for the selected option.
Example)
• After selecting the function for options, press and hold the K2 switch for 2 seconds. Edited value of the option will be
saved when entire segments blinks and tracking mode begins.
Option item
Input unit
SEG1
SEG2
SEG3
SEG4
Function
Setting to Cool or Heat only
mode
Main
0
0
0
0
Cooling and Heating (Factory default)
0
1
Only Cooling
0
2
Only Heating
Unused option
Main
0
1
0
0
Unused option
0
1
Unused option
Mixed mode indoor input
Main
0
2
0
0
Disabled (Factory default)
0
1
Enabled
Auto Change Over
Main
0
3
0
0
Disabled
0
1
Enabled (Factory default)
Channel address
Main
0
4
A
U
Automatic setting (Factory default)
00 ~ 15
Manual setting
CAUTION
• Edited option will not be saved if you do not end the option setting as explained in above instruction.
※ While you are setting the option, you may press and hold the K1 button to reset the value to previous setting.
※ If you want to restore the setting to factory default, press and hold the K4 button while you are in the option setting mode.
‐
If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored
setting is saved. Press and hold the K2 button. When the segments shows that tracking mode is in progress,
setting will be saved.
DB68-12535A-00_IM_23Y FJM Outdoor_AA_EN_.indd 24
DB68-12535A-00_IM_23Y FJM Outdoor_AA_EN_.indd 24
2023-09-22 오후 1:46:58
2023-09-22 오후 1:46:58